Plan Review Notes
Plan Review Notes For Permit 23041200
Permit Number 23041200
Review Stop G
Sequence Number 1
Notes
Date Text
2023-06-01 08:47:151ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 23041200
 6/1/23
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-1 & P-2: TO HELP EXPEDITE THE REVIEW PLEASE
 SHOW THE NEW GAS PIPING POINT OF CONNECTION TO THE
 EXISTING- SEC. 402.3 FBC FG.
  
 2) P-1 & P-2: LABEL THE REGULATORS AT THE APPLIANCES AS
 NEW OR EXISTING AND CLARIFY IF THEY ARE EQUIPPED WITH
 LEAK LIMITING DEVICES OR WILL REQUIRE VENTS TO THE
 OUTDOORS- SEC. 410.2 (4) FBC FG. PROVIDE DETAILS FOR
 VENTS IF REQUIRED- SEC. 410.3 & 410.3.1.
  
 3) P-1 & P-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE NEW APPLIANCES USING ONE OF THE METHODS PRESCRIBED
 IN SECS. 305.5- 304.9 FBC FG. PLEASE NOTE IF USING THE
 STANDARD METHOD THE MINIMUM REQUIRED VOLUME SHALL BE 50
 CU. FT. PER 1,000 BTUH OF THE APPLIANCE INPUT RATINGS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  