Plan Review Notes
Plan Review Notes For Permit 23041197
Permit Number 23041197
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-05 08:32:25 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) VALUE OF PROJECT IS SUPER LOW FOR A SUPER CHARGER.
 PLEASE SUBMIT A COST BREAKDOWN OF THE EQUIPMENT AND
 LABOR FOR A COMPLETE JOB.INCLUDE ALL MATERIALS SUPPLIED
 BY CUSTOMER AND OR CONTRACTOR.
  
 2) COR-FLEX CONDUIT PLEASE SUBMIT THE LISTING FOR THIS
 PRODUCT. 110.3
  
 3) PROVIDE CUT SHEETS FOR PEDESTALS SHOWING LISTING
 110.3, 625.5
  
 4) PROVIDE LISTING FOR ALL EQUIPMENT SUPERCHARGER V3
 110.3, 625.5
  
 5) PROVIDE COMPLIANCE WITH 625.43 FOR THE DISCONNECTING
 MEANS FOR THESE PEDESTALS.