2023-07-13 10:13:082ND REVIEW FBC-2020 PLUMBING
 PERMIT- 23041184
 7/13/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED 1ST REVIEW COMMENTS
 #3, 3A, 13, & 15 ARE LISTED WITH ADDITIONAL NOTES FOR
 FURTHER CLARIFICATION. NEW COMMENTS LISTED ARE BASED ON
 DESIGN CHANGES TO THE ORIGINAL PLANS.
  
 3) FAILED. P1.0 WATER HEATER DETAIL: THE THERMOSTAT
 CONTROL ON THE WATER HEATER CANNOT BE THE LIMITING
 DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE A DETAIL
 FOR A LIMITING DEVICE SUCH AS A MASTER THERMOSTATIC
 MIXING VALVE FOR THE PURPOSE OF HOT WATER DELIVERY-
 SEC. 607.1.1 FBC P.
 REQUIRED MASTER THERMOSTATIC MIXING VALVES AT WATER
 HEATERS NOT PROVIDED.
  
 A) REFER TO SEC. 468.3.5.1.2 FBC B: POINT OF USE MIXING
 VALVES SHALL BE INSTALLED AT ALL HANDWASH SINKS AND
 LAVATORIES TO LIMIT THE HOT WATER DELIVERY TEMPERATURE
 TO 110 DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE
 VALVES SPECIFIED IN THE SCHEDULE.
 REQUIRED POINT OF USE MIXING VALVES AT SINKS NOT
 PROVIDED.
  
 16) FAILED. PROVIDE THE COMPLIANCE DATA FOR THE WATER
 HEATERS ON THE ENERGYGAUGE FORM- SEC. C101.5.1 FBC EC.
 REQUIRED COMPLIANCE DATA NOT PROVIDED.
  
 NEW COMMENTS
  
 1) SHEETS P1.0, A-101, A-101, A-104, & A-504: THE
 LEADING EDGES OF DRINKING FOUNTAINS ARE PROTRUDING INTO
 THE CIRCULATION PATHS.THE FOUNTAINS SHALL EITHER BE
 EQUIPPED WITH CANE APRONS, PROVIDED WITH BARRIERS ON
 THE SIDES, OR INSTALLED IN NICHES- SEC. 307.2 FBC ACC.
 A) PLEASE ACCURATELY SHOW THE SPOUT HEIGHTS OF THE
 WHEELCHAIR ACCESSIBLE FOUNTAIN AND THE FOUNTAIN FOR
 STANDING PERSONS- SECS. 602.4- 602.7 FBC ACC.
  
 2) A-102: THE REVISED FLOOR PLAN SHOWS NEW 5 CHEMISTRY
 SINKS IN THE SCIENCE CLASSROOM. PLEASE REFER TO SEC.
 212.3 FBC ACC- A MINIMUM OF ONE SINK SHALL BE
 ACCESSIBLE AND INSTALLED IN COMPLIANCE WITH SECS.
 606.2, 606.3, 606.4 & 606.5. PLEASE PROVIDE COMPLIANCE
 DETAILS ON THE PLANS.
  
 3) P-1.0, P-3.2, & P-5.1: CHEMICAL WASTE FROM THE
 CHEMISTRY SINKS SHALL NOT DISCHARGE INTO THE SANITARY
 SYSTEM UNTIL THE WASTE HAS EITHER BEEN THOROUGHLY
 DILUTED, NEUTRALIZED OR TREATED BY PASSING THROUGH AN
 APPROVED DILUTION OR NEUTRALIZING DEVICE- SECS. 803.1 &
 803.2 FBC P. PLEASE PROVIDE COMPLIANCE DERTILS ON THE
 PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  