Plan Review Notes
Plan Review Notes For Permit 23041184
Permit Number 23041184
Review Stop B
Sequence Number 2
Notes
Date Text
2023-07-13 15:53:00BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE GUARD RAIL LOCATIONS (3RD FLOOR HALL
 WAY, STAIR PLATFORMS OVERLOOKING "TIMBER HALL", ETC.) -
 FBC 1015.2
  
 2) DRAWING A-415 DETAIL 1 - PLEASE SHOW THE REQUIRED
 HAND RAILS FOR BOTH SIDES OF THE STAIR FROM THE "TIMBER
 HALL" - 1011.11 HANDRAILS. FLIGHTS OF STAIRWAYS SHALL
 HAVE HANDRAILS ON EACH SIDE AND SHALL COMPLY WITH
 SECTION 1014.
  
 3) DRAWING A-413 AND A-411 - PLEASE SHOW THE BOTTOM
 HAND RAIL TO CONTINUE TO SLOPE - FBC 1014.6 WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 4) PLEASE SHOW RESTROOM CEILING TO COMPLY WITH FBC
 468.3.5.10 CEILINGS.
 CEILINGS IN GROUP TOILET ROOMS, KITCHENS, SCULLERIES,
 CAN WASH AREAS, SHOWERS AND LOCKER ROOMS SHALL BE
 IMPERVIOUS.
  
 5) DOOR 113 IS SHOWN ON THE DOOR SCHEDULE AS 9 FOOT
 WIDE - (PLEASE CLARIFY) THE MAXIMUM DOOR WIDTH IS 4
 FOOT PER FBC 1010.1.1
  
 6) PLEASE SHOW RESTROOM AND MOP SINK WALL FINISHES TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 7) DRAWINGS SAY TO SEE THE ENERGY CALCS. FOR EXTERIOR
 WALL INSULATION - THE ENERGY CALCS. PROVIDED DO NOT
 APPEAR TO SHOW THE CORRECT EXTERIOR WALL CONFIGURATION
 (2X4 WALLS WITH R-11) ?
  
 8) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE WIND
 DESIGN - FBC 1603.1.4
  
 9) THE BUILDING IS A RISK CATEGORY III PER FBC TABLE
 1604.5
  
 10) THE CHANGE OF OCCUPANCY TO A HIGHER RISK CATEGORY
 REQUIRES A WIND DESIGN ANALYSIS REPORT SIGNED AND
 SEALED FROM A DESIGN PROFESSIONAL - FBC EXISTING
 BUILDING 1007.2 SNOW AND WIND LOADS.
 BUILDINGS AND STRUCTURES SUBJECT TO A CHANGE OF
 OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF OCCUPANCY
 RESULTS IN HIGHER WIND OR SNOW RISK CATEGORIES BASED ON
 THE FLORIDA BUILDING CODE, BUILDING TABLE 1604.5,
 (HIGH-VELOCITY HURRICANE ZONES SHALL COMPLY WITH
 SECTION 1620) SHALL BE ANALYZED AND SHALL COMPLY WITH
 THE APPLICABLE WIND OR SNOW LOAD PROVISIONS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 11) PLEASE SHOW THE TERMITE PROTECTION TYPE PER FBC
 1816
  
 12) DRAWING LS-101 SHOWS A CLASS ROOM WITH 1078 SQ.FT.
 AND 54 OCCUPANTS - 2 MEANS OF EGRESS WOULD BE REQUIRED
 FOR THAT SPACE - FBC 1006.2.1
  
 13) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL13303 (SKY LIGHT) FBC 107.2.1
  
 14) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL18413 (DOOR) FBC 107.2.1
  
 15) PLEASE PROVIDE THE FRONT PAGES FOR PRODUCT APPROVAL
 FL20877 (STOREFRONT WALL) FBC 107.2.1
  
 16) PRODUCT APPROVAL PROVIDED FOR THE ROOFING SYSTEM =
 IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL - ROOFING SYSTEM TO BE USED ON
 THE PROVIDED PRODUCT APPROVAL MAY REQUIRE ADDITIONAL
 SIGNED AND SEALED ATTACHMENT DETAILS FROM AN ARCHITECT
 OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH REQUIRE A
 HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE PRODUCT
 APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 ON THE
 PRODUCT APPROVAL.
  
 17) THE DRAWING A-100.1 SHOWS CLOSER PARKING SPACES -
 PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING AND SIDEWALKS TO THE ACCESSIBLE ENTRY - FBC A
 208.3LOCATION. PARKING SPACES COMPLYING WITH 502 THAT
 SERVE A PARTICULAR BUILDING OR FACILITY SHALL BE
 LOCATED ON THE SHORTEST ACCESSIBLE ROUTE FROM PARKING
 TO AN ENTRANCE COMPLYING WITH 206.4
 FBC A 208.1.2 - A FACILITY THAT IS MAKING ALTERATIONS
 UNDER SECTION 202 AS REQUIRED BY S.303(A) OF THE
 AMERICANS WITH DISABILITES ACT OF 1990 MUST COMPLY WITH
 SECTION 208 TO THE MAXIMUM EXTENT FEASIBLE.