Text |
| 2023-05-22 12:10:09 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23041184 |
| | 5/22/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A101: THE PLUMBING FIXTURE CALCULATIONS ON |
| | A-101 INDICATE 7 DRINKING FOUNTAINS PROVIDED HOWEVER |
| | THE PLUMBING PLANS ARE SHOWING ONLY SIX- TABLE 403.1 |
| | FBC P. PLEASE NOTE THE ARCHITECTURAL AND LIFE SAFETY |
| | PLANS DO NOT SHOW THE DRINKING FOUNTAIN LOCATIONS ON |
| | THE FLOOR PLANS- SEC. 107.2.1 WPB. |
| | |
| | 2) P1.0, P2.1, P2.2, P2.3: REFER TO 468.3.5.6 FBC B AND |
| | PROVIDE HOSE BIBS IN EACH MALE AND FEMALE GROUP TOILET |
| | ROOM. |
| | |
| | 3) P1.0 WATER HEATER DETAIL: THE THERMOSTAT CONTROL ON |
| | THE WATER HEATER CANNOT BE THE LIMITING DEVICE FOR HOT |
| | WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING |
| | DEVICE SUCH AS A MASTER THERMOSTATIC MIXING VALVE FOR |
| | THE PURPOSE OF HOT WATER DELIVERY- SEC. 607.1.1 FBC P. |
| | A) REFER TO SEC. 468.3.5.1.2 FBC B: POINT OF USE MIXING |
| | VALVES SHALL BE INSTALLED AT ALL HANDWASH SINKS AND |
| | LAVATORIES TO LIMIT THE HOT WATER DELIVERY TEMPERATURE |
| | TO 110 DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE |
| | VALVES SPECIFIED IN THE SCHEDULE. |
| | |
| | 4) P1.0: CORRECT THE SUMP INSTALLATION DETAIL SHOWING |
| | THE DRAINAGE TO THE STORM DRAIN. THE DRAINAGE SHALL |
| | DISCHARGE TO THE SANITARY AS SHOWN ON THE ISOMETRIC |
| | DRAWING- SEC. 712.1 FBC P. A) PLEASE NOTE AN OIL |
| | SEPARATOR SHALL BE INSTALLED FOR THE SUMP PUMP DRAINAGE |
| | UNLESS AN APPROVED ALARM SYSTEM IS PROVIDED- SEC. |
| | 1003.4. |
| | |
| | 5) P2.1, P2.2: PLEASE CONFIRM HOT WATER WILL NOT BE |
| | PROVIDED TO THE EMERGENCY SHOWER AND EYE WASH STATIONS. |
| | PLEASE NOTE IF HOT WATER IS PROVIDED AN ASSE 1071 |
| | MIXING VALVE IS REQUIRED TO LIMIT THE HOT WATER |
| | TEMPERATURE TO ISEA Z358.1 SPECIFICATIONS- SEC. 411.1 |
| | FBC P. |
| | |
| | 6) P3.1: NOTE 1 SHOWS THE SANITARY DRAINAGE CONNECTING |
| | TO THE EXISTING LINE IN LIFT 110 SPACE. IS THIS A TYPO? |
| | PLEASE SHOW THE EXISTING LINE RUN ON THE DRAWING AND IN |
| | THE ISOMETRIC DRAWING ON P5.1- SEC. 107.2.1 WPB. A) |
| | PLEASE SHOW A NEW OR EXISTING SUMP PUMP AND PIT FOR |
| | LIFT 110 AND PROVIDE DRAINAGE DETAILS- SECS. 712.1 & |
| | 1003.4 FBC P. |
| | |
| | 7) P1.0 & P3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | NEUTRALIZER TANK AND SUBMIT MANUFACTURER SPECIFICATIONS |
| | AND INSTALLATION GUIDELINES- SEC. 803.1 FBC P. |
| | |
| | 8) P3.1, P3.2, P3.3, P5.1: PLEASE PROVIDE DRAIN AND |
| | VENT PIPE SIZES- SECS. 710.1 & 901.2.1 FBC P. |
| | |
| | 9) P4.1 & P5.1: PLEASE SHOW A MINIMUM OF ONE BUILDING |
| | DRAIN VENT PIPE EXTENDING TO THE OUTDOORS- SEC. 904.1 |
| | FBC P. |
| | |
| | 10) P5.1: PLEASE PROVIDE A WATER RISER DRAWING- SEC. |
| | 107.3.5.1.3 WPB. |
| | |
| | 11) A500: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE REQUIRED ACCESSIBLE URINAL- SECS. |
| | 213.3.3 & 605.3 FBC ACC. |
| | |
| | 12) A501: THE DOORS SHALL NOT SWING INTO THE CLEAR |
| | FLOOR SPACES REQUIRED FOR THE WATER CLOSETS- SEC. |
| | 603.2.3 FBC ACC. PLEASE SEE EXCEPTION 1 AND CORRECT THE |
| | PLAN. |
| | |
| | 13) A502 & A504: PLEASE ACCURATELY SHOW THE CENTERLINES |
| | OF THE WATER CLOSETS FROM THE SIDE WALLS- SEC. 604.2 |
| | FBC ACC- 16 INCHES MINIMUM 18 INCHES MAXIMUM. |
| | |
| | 14) A504: SHOW THE CENTERLINES OF THE TOILET PAPER |
| | DISPENSERS MEASURED FROM THE FRONTS OF THE WATER |
| | CLOSETS- SEC. AND FIGURE 604.7 FBC ACC. |
| | |
| | 15) A504: SHOW THE MOUNTING HEIGHTS OF GRAB BARS FOR |
| | THE WATER CLOSETS MEASURED TO THE TOPS OF THE GRIPPING |
| | SURFACES- SEC. 609.4 FBC ACC. |
| | |
| | 16) PROVIDE THE COMPLIANCE DATA FOR THE WATER HEATERS |
| | ON THE ENERGYGAUGE FORM- SEC. C101.5.1 FBC EC. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |