Plan Review Notes
Plan Review Notes For Permit 23041184
Permit Number 23041184
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-22 12:10:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23041184
 5/22/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A101: THE PLUMBING FIXTURE CALCULATIONS ON
 A-101 INDICATE 7 DRINKING FOUNTAINS PROVIDED HOWEVER
 THE PLUMBING PLANS ARE SHOWING ONLY SIX- TABLE 403.1
 FBC P. PLEASE NOTE THE ARCHITECTURAL AND LIFE SAFETY
 PLANS DO NOT SHOW THE DRINKING FOUNTAIN LOCATIONS ON
 THE FLOOR PLANS- SEC. 107.2.1 WPB.
  
 2) P1.0, P2.1, P2.2, P2.3: REFER TO 468.3.5.6 FBC B AND
 PROVIDE HOSE BIBS IN EACH MALE AND FEMALE GROUP TOILET
 ROOM.
  
 3) P1.0 WATER HEATER DETAIL: THE THERMOSTAT CONTROL ON
 THE WATER HEATER CANNOT BE THE LIMITING DEVICE FOR HOT
 WATER DELIVERY. PLEASE PROVIDE A DETAIL FOR A LIMITING
 DEVICE SUCH AS A MASTER THERMOSTATIC MIXING VALVE FOR
 THE PURPOSE OF HOT WATER DELIVERY- SEC. 607.1.1 FBC P.
 A) REFER TO SEC. 468.3.5.1.2 FBC B: POINT OF USE MIXING
 VALVES SHALL BE INSTALLED AT ALL HANDWASH SINKS AND
 LAVATORIES TO LIMIT THE HOT WATER DELIVERY TEMPERATURE
 TO 110 DEGREES F. PLEASE ADD THE LISTING NUMBERS OF THE
 VALVES SPECIFIED IN THE SCHEDULE.
  
 4) P1.0: CORRECT THE SUMP INSTALLATION DETAIL SHOWING
 THE DRAINAGE TO THE STORM DRAIN. THE DRAINAGE SHALL
 DISCHARGE TO THE SANITARY AS SHOWN ON THE ISOMETRIC
 DRAWING- SEC. 712.1 FBC P. A) PLEASE NOTE AN OIL
 SEPARATOR SHALL BE INSTALLED FOR THE SUMP PUMP DRAINAGE
 UNLESS AN APPROVED ALARM SYSTEM IS PROVIDED- SEC.
 1003.4.
  
 5) P2.1, P2.2: PLEASE CONFIRM HOT WATER WILL NOT BE
 PROVIDED TO THE EMERGENCY SHOWER AND EYE WASH STATIONS.
 PLEASE NOTE IF HOT WATER IS PROVIDED AN ASSE 1071
 MIXING VALVE IS REQUIRED TO LIMIT THE HOT WATER
 TEMPERATURE TO ISEA Z358.1 SPECIFICATIONS- SEC. 411.1
 FBC P.
  
 6) P3.1: NOTE 1 SHOWS THE SANITARY DRAINAGE CONNECTING
 TO THE EXISTING LINE IN LIFT 110 SPACE. IS THIS A TYPO?
 PLEASE SHOW THE EXISTING LINE RUN ON THE DRAWING AND IN
 THE ISOMETRIC DRAWING ON P5.1- SEC. 107.2.1 WPB. A)
 PLEASE SHOW A NEW OR EXISTING SUMP PUMP AND PIT FOR
 LIFT 110 AND PROVIDE DRAINAGE DETAILS- SECS. 712.1 &
 1003.4 FBC P.
  
 7) P1.0 & P3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE
 NEUTRALIZER TANK AND SUBMIT MANUFACTURER SPECIFICATIONS
 AND INSTALLATION GUIDELINES- SEC. 803.1 FBC P.
  
 8) P3.1, P3.2, P3.3, P5.1: PLEASE PROVIDE DRAIN AND
 VENT PIPE SIZES- SECS. 710.1 & 901.2.1 FBC P.
  
 9) P4.1 & P5.1: PLEASE SHOW A MINIMUM OF ONE BUILDING
 DRAIN VENT PIPE EXTENDING TO THE OUTDOORS- SEC. 904.1
 FBC P.
  
 10) P5.1: PLEASE PROVIDE A WATER RISER DRAWING- SEC.
 107.3.5.1.3 WPB.
  
 11) A500: PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR THE REQUIRED ACCESSIBLE URINAL- SECS.
 213.3.3 & 605.3 FBC ACC.
  
 12) A501: THE DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACES REQUIRED FOR THE WATER CLOSETS- SEC.
 603.2.3 FBC ACC. PLEASE SEE EXCEPTION 1 AND CORRECT THE
 PLAN.
  
 13) A502 & A504: PLEASE ACCURATELY SHOW THE CENTERLINES
 OF THE WATER CLOSETS FROM THE SIDE WALLS- SEC. 604.2
 FBC ACC- 16 INCHES MINIMUM 18 INCHES MAXIMUM.
  
 14) A504: SHOW THE CENTERLINES OF THE TOILET PAPER
 DISPENSERS MEASURED FROM THE FRONTS OF THE WATER
 CLOSETS- SEC. AND FIGURE 604.7 FBC ACC.
  
 15) A504: SHOW THE MOUNTING HEIGHTS OF GRAB BARS FOR
 THE WATER CLOSETS MEASURED TO THE TOPS OF THE GRIPPING
 SURFACES- SEC. 609.4 FBC ACC.
  
 16) PROVIDE THE COMPLIANCE DATA FOR THE WATER HEATERS
 ON THE ENERGYGAUGE FORM- SEC. C101.5.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  