| 2023-05-22 12:38:00 | 1ST REVIEW FBC-2020 FUEL GAS |
| | PERMIT- 23041184 |
| | 5/22/23 |
| | |
| | CODES IN EFFECT: |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS P2.1 & P3.1: PROVIDE A COMPLETE GAS RISER |
| | DRAWING AS REQUIRED BY SEC. 107.3.5.1.5 WPB. THE GAS |
| | RISER SHALL INCLUDE THE FOLLOWING INFORMATION PER SEC. |
| | 402.2 FBC FG. |
| | A) DELIVERY PRESSURE AT THE METER. |
| | B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| | C) TYPES AND SIZES OF PIPING. |
| | D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| | TO THE MOST REMOTE APPLIANCE OUTLET. |
| | E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| | F) LOCATIONS OF REGULATORS AND SHUTOFF VALVES, AND |
| | REGULATOR VENT PIPING DETAILS (IF APPLICABLE). |
| | G) OUTLET PRESSURES AT REGULATORS. |
| | H) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| | I) PIPE SIZING TABLES. |
| | |
| | 2) P3.1: SHOW THE LOCATIONS OF THE GAS APPLIANCES ON |
| | THE FLOOR PLAN AND ADD NOTES TO IDENTIFY THEM- SEC. |
| | 107.2.1 WPB. |
| | |
| | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW GAS |
| | APPLIANCES AND INDICATE HOW THE AIR WILL BE PROVIDED- |
| | SEC. 304.1 FBC FG. |
| | |
| | 4) PROVIDE VENTING PLANS AND SPECIFICATIONS FOR THE |
| | APPLIANCES INCLUDING A DIAGRAM SHOWING THE TYPES AND |
| | SIZES OF VENTS, VENT RUNS, AND TERMINATION LOCATIONS- |
| | SECS. 502.1 & 503.1 FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |