Plan Review Notes
Plan Review Notes For Permit 23041184
Permit Number 23041184
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-05-09 14:24:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NUMEROUS STAIRS LOCATED THROUGHOUT THIS
 EDUCATIONAL OCCUPANCY.
  
 14.2.1 GENERAL.
  
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7 AND
 SECTION 14.2
  
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR FIRST GRADE STUDENTS SHALL BE LOCATED
 ON A LEVEL OF EXIT DISCHARGE, UNLESS OTH ERWISE
 PERMITTED BY 14.2.1.4.
  
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL NOT
 BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF EXIT
 DISCHARGE, UNLESS
 OTHERWISE PERMITTED BY 14.2.1.4
  
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS SPECIFIED
 IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED TO BE USED
 WHERE PROVIDED
 WITH INDEPENDENT MEANS OF EGRESS DEDICATED FOR USE BY
 THE PRESCHOOL,
 KINDERGARTEN, FIRST-GRADE, OR SECOND-GRADE STUDENTS
  
 HOW IS IT INSURED THAT STUDENTS OF CERTAIN AGES WILL
 NOT BE USING AREAS WITH STAIRS?
  
  
  
 2) SHEET LS 103 - THERE IS AN INDICATION OF A
 MEZZANINCE ROOM
  
 3.3.184 MEZZANINE. AN INTERMEDIATE LEVEL BETWEEN THE
 FLOOR AND THE
 CEILING OF ANY ROOM OR SPACE. (SAF-FIR)
  
 14.2.1 GENERAL.
  
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7 AND
 SECTION 14.2
  
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR FIRST GRADE
 STUDENTS SHALL BE LOCATED ON A LEVEL OF EXIT DISCHARGE,
 UNLESS OTH ERWISE PERMITTED BY 14.2.1.4.
  
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL NOT
 BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF EXIT
 DISCHARGE, UNLESS
 OTHERWISE PERMITTED BY 14.2.1.4
  
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS SPECIFIED
 IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED TO BE USED
 WHERE PROVIDED
 WITH INDEPENDENT MEANS OF EGRESS DEDICATED FOR USE BY
 THE PRESCHOOL,
 KINDERGARTEN, FIRST-GRADE, OR SECOND-GRADE STUDENTS.
  
 HOW IS IT INSURED THAT STUDENTS WILL NOT BE USING THESE
 SPACES?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET LS 103 - THERE IS AN INDICATION OF A
 MEZZANINCE ROOM WITH A SINGLE EXIT.
  
 PER NFPA 101
  
 7.4.1 GENERAL.
  
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE,
 STORY, OR PORTION THEREOF SHALL BE NOT LESS THAN TWO,
 EXCEPT UNDER ONE OF
 THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN
 CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR
 BALCONY WHERE THE COMMON PATH OF TRAVEL LIMITATIONS OF
 CHAPTERS 11 THROUGH 43 ARE MET.
  
 14.2.5.3.1 COMMON PATH OF TRAVEL SHALL NOT EXCEED 100
 FT (30 M) IN A
 BUILDING PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 9.7
  
 PLEASE PROVIDE THE TRAVEL DISTANCE INDCATING COMPLIANCE
 WITH THE REQUERMENT.
  
  
  
 4) SHEET A 101 THRU 104 - THERE ARE INDICATIONS OF
 LIFTS, WHICH APPEAR TO BE ELEVATORS.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER'S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE OR
 JUSTIFY WITH SPECITICDETAILED NARRATIVE AND CODE
 REFERENCES
  
  
  
 5) LIFE SAFETY SHEETS - THERE ARE NO INDICATIONS OF
 AREAS OF REFUGE.
  
 AREAS OF REFUGE SHALL COMPLY WHERE APPLICABLE PER THE
 BUILDING CODE AND NFPA 101, CH 7, MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) LIFE SAFETY SHEETS - EMERGENCY RADIO SIGNAL STRENGTH
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH
 FIRE DEPARTMENT. TESTING SHALL BE DONE BY FIRE
 INSPECTOR PORTABLE RADIOS.
  
 IF THE MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL
 AMPLIFIED SYSTEM SHALL BE INSTALLED UNDER SEPARATE
 PERMIT WITH A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 ANY SYSTEM SHALL NOT BE INSTALLED WITHOUT CONTACTING
 AND COORDINATION WITH MARK FILLA, PALM BEACH COUNTY
 PUBLIC SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT TO
 COMPLY.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  