Plan Review Notes
Plan Review Notes For Permit 23041184
Permit Number 23041184
Review Stop B
Sequence Number 1
Notes
Date Text
2023-06-01 09:22:36BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THERE ARE STRUCTURAL DRAWINGS LISTED ON THE COVER
 SHEET WHICH ARE NOT IN PROJECTDOX - FBC WPB 107.2
  
 2) DRAWING LS-101 UNDER "EXIT CAPACITY GROUND LEVEL" -
 EXIT NUMBER 113 IS NOTED BUT IS NOT SHOWN ON THE
 DRAWINGS - PLEASE CLARIFY
  
 3) PLEASE PROVIDE AN EXISTING FLOOR PLAN.
  
 4) PLEASE DESCRIBE THE ROOM (110) OR THE ITEM LABELED
 "LIFT" .
  
 5) PLEASE PROVIDE GUARD RAIL DETAILS - FBC 1015.2
  
 6) PLEASE SHOW THE ROOF HATCH DISTANCE FROM THE
 BUILDING EDGE - FBC 1015.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN SIDE OF A
 WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, ROOF OR
 GRADE BELOW.
  
 7) PLEASE SHOW THE REQUIRED HAND RAILS FOR BOTH SIDES
 OF THE GRAND STAIR - 1011.11 HANDRAILS. FLIGHTS OF
 STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE AND SHALL
 COMPLY WITH SECTION 1014.
  
 8) DRAWING A-413 - PLEASE SHOW THE BOTTOM HAND RAIL TO
 CONTINUE TO SLOPE (ONE SIDE OF THE SECTION SHOWS THE
 HAND RAIL TO SLOPE CORRECTLY) - FBC 1014.6 WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY NOT LESS THAN 12
 INCHES (305 MM) BEYOND THE TOP RISER AND CONTINUE TO
 SLOPE FOR THE DEPTH OF ONE TREAD BEYOND THE BOTTOM
 RISER.
  
 9) PLEASE SHOW THE FIRE RATED WALLS DESIGN ASSEMBLY (UL
 NUMBERS) - FBC 703.3
  
 10) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTEIOR WINDOWS AND DOORS
 - ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 11) PLEASE SHOW THE BUILDING SET BACKS FROM THE
 PROPERTY LINES - A SITE PLAN SHOULD INCLUDE THE
 FOLLOWING - FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 12) EXTERIOR DOORS SHALL NOT ENCROACH INTO OTHER
 PROPERTIES - FBC 3202.2 ENCROACHMENTS ABOVE GRADE AND
 BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 13) PLEASE SHOW THE REQUIRED FIRE RATING FOR THE RATED
 DOOR ON THE DOOR SCHEDULE - FBC 716
  
 14) PLEASE SHOW REQUIRED DOOR CLOSURES -
 FBC 468.3.5.3.3 TOILET ROOMS ADJACENT TO FOOD
 PREPARATION OR DINING AREAS SHALL BE COMPLETELY
 ENCLOSED, HAVE SELF-CLOSING DOORS, AND SHALL OPEN INTO
 VESTIBULES WITH SELF-CLOSING DOORS.
 FBC 716.5.9 DOOR CLOSING. FIRE DOORS SHALL BE LATCHING
 AND SELF- OR AUTOMATIC-CLOSING IN ACCORDANCE WITH THIS
 SECTION.
  
 15) PLEASE SHOW RESTROOM CEILING TO COMPLY WITH FBC
 468.3.5.10 CEILINGS.
 CEILINGS IN GROUP TOILET ROOMS, KITCHENS, SCULLERIES,
 CAN WASH AREAS, SHOWERS AND LOCKER ROOMS SHALL BE
 IMPERVIOUS.
  
 16) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET PAPER
 DISPENSER LOCATIONS PER FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
  
 17) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS
 "REFLECTIVE SURFACE" WHEN REFERING TO THE MIRROR
 LOCATIONS - FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 18) ACCESSIBLE RESTROOM = PLEASE SHOW THE TOILET GRAB
 BAR HEIGHT TO THE TOP OF THE GRIPPING SURFACE (NOT THE
 CENTER) - FBC A 609.4POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE
  
 19) PLEASE SHOW THE ACCESSIBLE ROUTE TO THE GRAND STAIR
 BALCONY MEETING PLACES - FBC A 206.2.3 MULTI-STORY
 BUILDINGS AND FACILITIES.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT EACH STORY
 AND MEZZANINE IN MULTI-STORY BUILDINGS AND FACILITIES.
  
 20) PLEASE SHOW THE USE FOR THE TOWER ROOM AND THE
 ACCESSIBLE ROUTE - FBC A 206.2.3 MULTI-STORY BUILDINGS
 AND FACILITIES.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT EACH STORY
 AND MEZZANINE IN MULTI-STORY BUILDINGS AND FACILITIES.
  
 21) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE
 ACCESSIBLE PARKING AND SIDEWALKS TO THE ACCESSIBLE
 ENTRY - FBC 206.2.1 SITE ARRIVAL POINTS.
 AT LEAST ONE ACCESSIBLE ROUTE SHALL BE PROVIDED WITHIN
 THE SITE FROM ACCESSIBLE PARKING SPACES AND ACCESSIBLE
 PASSENGER LOADING ZONES; PUBLIC STREETS AND SIDEWALKS;
 AND PUBLIC TRANSPORTATION STOPS TO THE ACCESSIBLE
 BUILDING OR FACILITY ENTRANCE THEY SERVE.