| Plan Review Notes For Permit 23041178 |
| Permit Number |
23041178 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-07-17 13:16:09 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 607.1.1/613.1 - SHOW THE REQUIRED | | | THERMOSTATIC MIXING DEVICE IN THE WATER HEATER PIPING | | | DETAIL AND SHOW THAT ALL HOT WATER GOES THROUGH THE | | | DEVICE. THIS DEVICE SHOULD MEET THE ASSE 1017 STANDARD. | | | | | | 2. 2020 FPC 1003.3.1 - ONLY DEVICES DESIGNED TO RECEIVE | | | FATS, OILS AND GREASE SHALL BE DIRECTED TO THE GREASE | | | WASTE. PLEASE SHOW THAT THE ICE BIN, HAND SINKS AND | | | OTHER DEVICES THAT ARE NOT DESIGNED TO RECEIVE F.O.G | | | DISCHARGES ARE GOING TO THE SANITARY AND NOT TO THE | | | GREASE WASTE. | | | | | | 3. 2020 FPC 901.2.1 - - THE WATER CLOSET IN THE WOMEN'S | | | IS NOT VENTED TO CODE. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | |
|