| Plan Review Notes For Permit 23041099 |
| Permit Number |
23041099 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-05 13:37:24 | 1ST REVIEW FMC | | | PERMIT: 23041099 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) APPLIANCES IN A FLOOD ZONE WILL NEED TO COMPLY WITH | | | FRC M1401.5 | | | | | | 2) PROVIDE AN EXHAUST FAN FOR THE SHOWER/BATHTUB AREA | | | OF THE PRIMARY BATH. FRC R303.3 | | | | | | 3) PROVIDE THE RETURN AIR PATH FROM THE LIVING ROOM | | | BACK TO AHU-1. FRC M1602.3 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|