| Date |
Text |
| 2023-04-25 09:38:57 | 1ST GAS REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2020 FRC G2413.4.1 - THE PIPE SIZING IS NOT CORRECT. |
| | IF USING THE LONGEST RUN METHOD, EACH "SYSTEM" CAN USE |
| | ONLY ONE CHART AND BASE THE CALCULATIONS BASED ON THE |
| | LONGEST RUN. IF THE LONGEST RUN IS 155 FEET, THE NEXT |
| | AVAILABLE LINE WOULD BE 175 FEET. YOU WOULD NEED TO USE |
| | THE 175 FEET LINE. YOU CANNOT USE 4 DIFFERENT TABLES. |
| | EACH "SYSTEM" IS BASED ON THE LINE PRESSURE BETWEEN |
| | REGULATORS. |
| | |
| | 2. 2020 FRC G2413.4.1 - THE BTU LOAD ON THE FLOOR PLAN |
| | AND THE BTU LOAD ON THE ISOMETRIC DO NOT MATCH. THE |
| | GENERATOR IS SHOWN AS 604K ON THE ISO, AND 1202K ON THE |
| | FLOOR PLAN. |
| | |
| | 3. 2020 FRC G2413.4.1 - THE ISO SHOWS 1" P.E. AFTER THE |
| | METER ON THE WAY TO THE GENERATOR/WH/RANGE/POOL HEATER |
| | AND THE FLOOR PLAN SHOWS 3/4". PLEASE FIX. |
| | |
| | 4. 2020 FRC R303.5.1 - ALTHOUGH THE GENERATOR WILL |
| | REQUIRE ITS OWN SEPARATE PERMIT, THE GENERATOR WILL |
| | NEED TO BE 10 FEET FROM OPENINGS INTO THE STRUCTURE. |
| | PLEASE NOTE THAT THE GENERATOR WILL BE ON A SEPARATE |
| | PERMIT AND ADJUST ITS LOCATION TO BE 10 FEET FROM |
| | OPENINGS. |
| | |
| | 5. 2020 FRC G2427.8 - THE POOL HEATER EXHAUST WILL NEED |
| | TO BE 4 FEET FROM OPENINGS. IT APPEARS TO BE DIRECTLY |
| | UNDER A BEDROOM WINDOW. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | |