| 2023-06-21 13:33:14 | RESIDENTIAL(R3)REVISION. FIFTH BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #23041075 |
| | 234 EDGEWOOD DR (MAIN HOUSE ONLY). |
| | |
| | IMPORTANT: |
| | THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A |
| | SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS, |
| | INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT. |
| | |
| | 1- SHUTTERS PRODUCT APPROVALS SUBMITTED: |
| | |
| | PREVIOUS COMMENT: |
| | REPEAT COMMENT: SHUTTERS NOA 20-1102.06 WAS SUBMITTED |
| | BUT THE COMPLETE INSTALLATION SCHEDULE WAS NOT. PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. |
| | |
| | RESPONSE: |
| | SHUTTERS COMPLETE INSTALLATION SCHEDULE WAS NOT |
| | SUBMITTED. ONLY SHUTTER DETAIL DRAWING DRAWN BY THE |
| | ARCHITECT WAS SUBMITTED. THIS DRAWING DOESN'T PROVIDE |
| | THE COMPLETE SHUTTERS INSTALLATION INFORMATION REQUIRED |
| | BY THE CITY FOR ALL SHUTTERS INSTALLATION. SEE CITY |
| | SAMPLE. |
| | NOTE: THERE ARE TWO OPTIONS TO ADDRESS THIS COMMENT. |
| | ONE OPTION IS FOR CONTRACTOR TO SUBMIT SHUTTERS |
| | COMPLETE INSTALLATION SCHEDULE NOW OR THE OTHER OPTION |
| | IS FOR SHUTTERS CONTRACTOR TO SUBMIT ALL THE |
| | INFORMATION UNDER A SEPARATE PERMIT. (PRODUCT APPROVAL |
| | AND COMPLETE INSTALLATION SCHEDULE). |
| | CONTRACTOR TO ADVICE IN WRITING HOW ADDRESSING THIS |
| | COMMENT. THE SEPARATE SHUTTERS PERMIT OPTION WILL HELP |
| | TO APPROVE THIS REVISION UNDER THIS CONDITION. |
| | |
| | 2- SHUTTER DRAWING SUBMITTED WAS NOT SIGNED AND SEALED |
| | BY THE ARCHITECT. |
| | IT NEEDS THE ARCHITECT'S DIGITAL SIGNATURE AS DONE WITH |
| | ALL THE MASTER PERMIT DRAWINGS. ALL DOCUMENTS PREPARED |
| | BY A LICENSED ARCHITECT NEED TO HAVE THE ORIGINAL |
| | VERIFIABLE DIGITAL SIGNATURE OF THE ARCHITECT OF RECORD |
| | AS REQUIRED BY SEC. 61G1-16.003 F.A.C. AND CHAPTER 481 |
| | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC |
| | RECORDS. |
| | |
| | ARCHITECTS |
| | 61G1-16.005 PROCEDURES FOR DIGITALLY SIGNING AND |
| | SEALING AND FOR ELECTRONICALLY TRANSMITTING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. |
| | |
| | |
| | NOTE: ALL ROOFING PRODUCT APPROVALS ARE REVIEWED UNDER |
| | SEPARATE ROOFING PERMITS. NO NEED TO RESUBMIT UNDER |
| | THIS REVISION TO AVOID CONFLICTS/DELAYS. |
| | |