| 2023-05-22 18:14:55 | RESIDENTIAL(R3)REVISION. THIRD BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | REVISION #23041075 |
| | 234 EDGEWOOD DR |
| | |
| | IMPORTANT: |
| | THIS INFORMATION IS ONLY FOR THE MAIN HOUSE. THERE IS A |
| | SEPARATE PERMIT FOR THE GARAGE. ANY REVISIONS, |
| | INSPECTIONS NEED TO BE DONE UNDER THAT SEPARATE PERMIT. |
| | |
| | |
| | 1- PRODUCT APPROVALS SUBMITTED: |
| | C) NEW LOUVERED SHUTTERS AS SPECIFIED ON PLANS. AND, |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY |
| | SAMPLE. |
| | RESPONSE: |
| | PARTIALLY COMPLIED. NOA 20-1102.06 WAS SUBMITTED BUT |
| | THE COMPLETE INSTALLATION SCHEDULE WAS NOT. PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. |
| | |
| | |
| | D)HARDIE BOARD SIDING AS SPECIFIED ON PLANS. |
| | RESPONSE: |
| | NOA 17-0821.21 SUBMITTED EXPIRED ON MAY 1, 2022. NEED |
| | TO PROVIDE CURRENT PRODUCT APPROVAL. ARCHITECT TO |
| | REVIEW NEW PRODUCT APPROVAL BEFORE SUBMITTAL. |
| | |
| | |
| | E)BALCONY UNDERLAYMENT SPECIFIED ON PLANS FOR PROPOSED |
| | FINISH FLOOR. |
| | RESPONSE: |
| | PARTIALLY COMPLIED. NOA 22-0706.09 SUBMITTED. SELECTED |
| | ASSEMBLY ON PAGE 27 OF 32 IS GOOD FOR -52.5PSF MAXIMUM |
| | DESIGN PRESSURES. NEED TO PROVIDE SIGNED AND SEALED RAS |
| | 117 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 |
| | TO MEET THE DESIGN PRESSURES FOR ROOF ZONE #2 AND #3. |
| | SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA. |
| | ALSO, IDENTIFY WHICH FINISH PRODUCT FROM TABLE 4 OF |
| | SAME NOA IS GOING TO BE INSTALLED. |
| | |
| | F)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| | RESPONSE: |
| | ARCHITECT SPECIFIES PEEL & STICK WATERPROOFING ON SHEET |
| | A3.1. NOA 18-1109.03 SUBMITTED IS NOT A PEEL & STICK |
| | UNDERLAYMENT. PEEL AND STICK UNDERLAYMENT COMPLIES WITH |
| | CODE REQUIREMENT FOR ROOFING UNDERLAYMENT. IF USING |
| | OTHER TYPE OF UNDERLAYMENT, THEN ARCHITECT NEEDS TO |
| | REVISE PLANS SHOWING HOW COMPLYING WITH SEC. R905.1.1.1 |
| | FBC-RESIDENTIAL. THERE ARE FIVE OPTIONS. CLEARLY |
| | SPECIFY WHICH ONE. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |