| 2023-05-18 07:08:17 | 1ST PLUMBING REVIEW |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER NEEDS TO |
| | BE IN ISOMETRIC FORM. PLEASE SUBMIT AN ISOMETRIC RISER |
| | WITH FIXTURE TAGS ON EACH RISER. |
| | NOTE: SHOWING THE SECOND FLOOR DRAINAGE ON THE 1ST |
| | FLOOR PLAN MAKES IT DIFFICULT TO REVIEW. THE SECOND |
| | FLOOR DRAINS SHOULD BE SHOWN ON THE SECOND FLOOR PLAN |
| | IMPOSED UNDER THE FIXTURES THEY SERVE. |
| | |
| | 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SUPPLIED |
| | DOES NOT MATCH THE CURRENT LAYOUT. THE FLOOR PLAN SHOWS |
| | TUB-LAV-SHOWER-LAV, AND THE RISER SHOWS |
| | LAV-TUB-SHOWER-LAV. THEY SHOULD MATCH. |
| | |
| | 3. 2020 FRC P3108.2.1 - IT SHOULD BE NOTED THAT THE |
| | EXISTING IS SHOWN AS NOT BEING VENTED TO CODE. THE |
| | LAUNDRY IS NOT ALLOWED TO VENT THE BATHTUB AND WATER |
| | CLOSET. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |