Plan Review Notes
Plan Review Notes For Permit 23041073
Permit Number 23041073
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-18 07:08:171ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER NEEDS TO
 BE IN ISOMETRIC FORM. PLEASE SUBMIT AN ISOMETRIC RISER
 WITH FIXTURE TAGS ON EACH RISER.
 NOTE: SHOWING THE SECOND FLOOR DRAINAGE ON THE 1ST
 FLOOR PLAN MAKES IT DIFFICULT TO REVIEW. THE SECOND
 FLOOR DRAINS SHOULD BE SHOWN ON THE SECOND FLOOR PLAN
 IMPOSED UNDER THE FIXTURES THEY SERVE.
  
 2. 2017 WPB AMEND 107.3.5.3 (12) - THE RISER SUPPLIED
 DOES NOT MATCH THE CURRENT LAYOUT. THE FLOOR PLAN SHOWS
 TUB-LAV-SHOWER-LAV, AND THE RISER SHOWS
 LAV-TUB-SHOWER-LAV. THEY SHOULD MATCH.
  
 3. 2020 FRC P3108.2.1 - IT SHOULD BE NOTED THAT THE
 EXISTING IS SHOWN AS NOT BEING VENTED TO CODE. THE
 LAUNDRY IS NOT ALLOWED TO VENT THE BATHTUB AND WATER
 CLOSET.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  
  