| Date |
Text |
| 2023-06-30 11:37:20 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| | |
| | PLEASE ADDRESS PREVIOUS COMMENTS BELOW DATED 06/21/2023 |
| | AND RESUBMIT. |
| | |
| | 1. FBC B 107.2.1. PROVIDE THE FOLLOWING INFORMATION FOR |
| | FLORIDA PRODUCT APPROVAL FL14083-R28 FOR THE PROPOSED |
| | FLAT ROOF RECOVER SYSTEM TO BE USED CORRESPONDING TO |
| | ENGINEERS MEMBRANE ATTACHMENT CALCULATIONS. EVALUATION |
| | REPORT PAGES #1-5, INSTALLATION INSTRUCTIONS FOR SYSTEM |
| | R-79 PAGE #97. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| | DRAWINGS. SUBMITTED EVALUATION REPORT & INSTALLATION |
| | INSTRUCTIONS ARE FOR FL14083-R26. |
| | 2. FBC R 301 FAC9N-3. PROVIDE REROOF SYSTEM NUMBER & |
| | INSTALLATION INSTRUCTIONS PAGE FOR THE MAIN CENTER ROOF |
| | & LOWER NORTH ROOF AREAS TO BE REMOVED AND REPLACED AS |
| | PER THE SUBMITTED ROOF MOISTURE REPORT. PROVIDE SIGNED |
| | AND SEALED CALCULATIONS IF SYSTEM SELECTED DOES NOT |
| | MEET MINIMUM DESIGN PRESSURE REQUIREMENTS. PLEASE NOTE: |
| | PRODUCT APPROVAL FL14083-R28 WAS REVISED TO FL14083-R29 |
| | ON JUNE 20, 2023. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |