Plan Review Notes
Plan Review Notes For Permit 23041039
Permit Number 23041039
Review Stop G
Sequence Number 1
Notes
Date Text
2023-04-21 07:25:511ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FGC 503 - A SEPARATE HOOD PERMIT IS REQUIRED
 FOR THE APPLIANCES BEING INSTALLED. WHEN THE HOOD
 PERMIT IS APPLIED FOR, NOTIFY ME AND I CAN RELEASE THIS
 COMMENT.
  
 2. 2017 WPB AMEND 107.3.5.3 (13) - PLEASE SUBMIT A GAS
 RISER DIAGRAM THAT INCLUDES ANY OF THE FOLLOWING
 APPLICABLE ITEMS. LOCATION OF SHUT-OFFS, THE PIPING
 MATERIAL, GAS PIPE SIZING METHOD AND BTU LOADS,
 APPLIANCE SCHEDULE, THE TYPE OF GAS PROPOSED, LP TANK
 OR METER LOCATION, AND THE EXISTING GAS SYSTEM
 (LABELING EXISTING AND NEW FOR CLARITY). INCLUDE A
 FLOOR PLAN THAT SHOWS THE ROUTING OF THE GAS LINE.
  
 3. 2020 FGC 304 - INCLUDE THE COMBUSTION AIR
 CALCULATIONS FOR THE APPLIANCES AND BTU LOAD BEING
 INSTALLED.
  
 4. 2017 WPB AMENDS 107.2.1 - PLEASE HAVE THE PERSON WHO
 DESIGNED THE DRAWINGS PRINT THEIR NAME, SIGN THEIR
 NAME, AS WELL AS PUT THE CONTRACTOR'S NUMBER ON THE
 DRAWING AS REQUIRED BY THE WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved