| | PLEASE PROVIDE FOORING UNDELAYEMENT FBC PRODUCT |
| | APPROVAL AND SOUND TESTING RESULTS |
| | ALSO PROVIDE |
| | FLAME SPREAD REPORT FOR THE SELECTED UNDERLAYMENT AND |
| | ALL FLOORING MATERIAL FOR THE PROJECT. |
| | |
| | |
| | |
| | FLOORING SUBMITTAL |
| | ITEMS TO PROVIDE: |
| | 1. FLOOR PLAN LAYOUT TO SHOW DIMENSIONS, AREA AND TYPE |
| | OF FLOORING FOR EACH AREA. |
| | |
| | PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| | PROPOSED? |
| | |
| | 3. [FBC 1207.2]AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| | OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| | SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| | LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| | TESTED IN ACCORDANCE WITH ASTM E90. |
| | |
| | 4. [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES |
| | BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A |
| | DWELLING |
| | UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN |
| | THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS |
| | RATING OF |
| | NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| | WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E492. |
| | |
| | 5. [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | IF YOU HAVE ANY QUESTIONS OR CONCERNS PLEASE DO NOT |
| | HESITATE TO CONTACT US |
| | |
| | LOUIS BOND, AIA |
| | BUILDING PLANS EXAMINER II |
| | DEVELOPMENT SERVICES DEPT. |
| | BUILDING DIVISION |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FLORIDA 33401 |
| | PH: 561-805-6729 |
| | FX: 561-805-6676 |
| | EMAIL: [email protected] |
| | |