2023-06-16 17:13:581ST REVIEW FBC-2020 PLUMBING
 PERMIT- 23041009
 6/16/23
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-400.01: THE DISCHARGE FROM THE GREASE
 INTERCEPTOR SHALL BE DIRECTLY CONNECTED TO THE SANITARY
 DRAINAGE SYSTEM- SEC. 1003.3.8 FBC P. PLEASE PROVIDE A
 PIPING DETAIL THAT IS CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS AND SEC. 802.1 FBC P.
  
 A) A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF
 THE GREASE INTERCEPTOR AND AT A MINIMUM AN APPLICATION
 MUST BE SUBMITTED PRIOR TO PLUMBING PLAN APPROVAL. YOU
 CAN SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU
 DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER