Plan Review Notes
Plan Review Notes For Permit 23041007
Permit Number 23041007
Review Stop M
Sequence Number 1
Notes
Date Text
2023-05-03 12:01:441ST REVIEW FMC
 PERMIT: 23041007
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DRAWINGS SHOW THE EXISTING EXAM AND RESTROOM ARE
 TO BE REMOVED AND THE EXISTING WAITING ROOM IS TAKING
 THIS SQUARE FOOTAGE. PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THIS ENLARGED WAITING ROOM AND SHOW
 HOW THE ADDITIONAL OUTDOOR AIR IS TO BE INTRODUCED INTO
 THIS NEW AREA. FMC TABLE 403.3.1.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  