| 2023-05-30 15:03:48 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23041004 |
| | 5/30/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P-100: SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE |
| | WATER BACKFLOW PREVENTER AND THE GREASE INTERCEPTOR. AT |
| | A MINIMUM, THE PERMIT APPLICATIONS FOR EACH SHALL BE |
| | SUBMITTED PRIOR TO MAIN PLUMBING PLAN APPROVAL. IF |
| | CONTRACTORS ARE NOT CURRENTLY SELECTED FOR EACH |
| | INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED TBD |
| | (TO BE DETERMINED). EACH COMPLETED APPLICATION SHALL BE |
| | EMAILED TO [email protected] . YOU WILL THEN |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND |
| | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) P100: KEYNOTES 2, 3, 5, 8, & 10 REFER TO CIVIL |
| | DRAWINGS WHICH WERE NOT UPLOADED FOR REVIEW. PLEASE |
| | PROVIDE THE DRAWINGS- SEC. 107.2.1 WPB. |
| | |
| | 3) P-102: PROVIDE GUTTER AND DOWNSPOUT SIZES- TABLES |
| | 1106.3 & 1106.6 FBC P. |
| | |
| | 4) P-501: A MEANS OF LIMITING THE HOT WATER TEMPERATURE |
| | AT THE WATER HEATER OTHER THAN THE THERMOSTAT IS |
| | REQUIRED IN COMPLIANCE WITH SEC. 607.1.1 FBC P. PLEASE |
| | PROVIDE A MASTER THERMOSTATIC MIXING VALVE AND SHOW THE |
| | PIPING CONNECTIONS IN THE DETAIL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |