Plan Review Notes
Plan Review Notes For Permit 23040991
Permit Number 23040991
Review Stop E
Sequence Number 2
Notes
Date Text
2023-07-10 08:43:10ELECTRICAL REVIEW FAILED
  
 1) ELECTRICAL PLAN STILL DOES NOT DETAIL THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 WEST PALM BEACH AMENDMENT 107.2
  
 2) PLAN STILL DETAILS EQUIPMENT POWERED THROUGH AN
 ELECTRIC RECEPTACLE. STUXURE CONTROL BOX.
  
 NEC 400.12 USES NOT PERMITTED.
 UNLESS SPECIFICALLY PERMITTED IN 400.10, FLEXIBLE
 CABLES, FLEXIBLE CORD SETS, AND POWER SUPPLY CORDS
 SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
 .
  