Plan Review Notes
Plan Review Notes For Permit 23040991
Permit Number 23040991
Review Stop E
Sequence Number 1
Notes
Date Text
2023-05-19 12:50:00ELECTRICAL REVIEW FAILED
  
 1) ELECTRICAL PLAN IS REQUIRED TO BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 WEST PALM BEACH AMENDMENT 107.2
  
 2) PLAN DETAILS EQUIPMENT POWERED THROUGH AN ELECTRIC
 RECEPTACLE. EQUIPMENT.
 NEC 400.12 USES NOT PERMITTED.
 UNLESS SPECIFICALLY PERMITTED IN 400.10, FLEXIBLE
 CABLES, FLEXIBLE CORD SETS, AND POWER SUPPLY CORDS
 SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A
 STRUCTURE.
  
 3) PLEASE PROVIDE AN ELECTRICAL FLOOR/SITE PLAN
 LOCATING ALL EQUIPMENT SHOWN IN SCHEMATIC DRAWING. FBC
 107.2
  
 4) PLAN DETAILS AN NEW 225 AMP ELECTRIC PANEL. NOTES
 CONTAINED IN THIS PLAN INDICATE THIS PANEL TO BE
 INSTALLED BY OTHERS. PLEASE PROVIDE THE APPLICABLE
 PERMIT APPLICATION AND PLANS FOR NEW PANEL. FBC 107.2
  
 5) PLEASE PROVIDE DETAILS OF WIRE METHODS USED FOR ALL
 WIRING. NEC 110.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  