| Date |
Text |
| 2023-05-19 12:50:00 | ELECTRICAL REVIEW FAILED |
| | |
| | 1) ELECTRICAL PLAN IS REQUIRED TO BEAR THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | WEST PALM BEACH AMENDMENT 107.2 |
| | |
| | 2) PLAN DETAILS EQUIPMENT POWERED THROUGH AN ELECTRIC |
| | RECEPTACLE. EQUIPMENT. |
| | NEC 400.12 USES NOT PERMITTED. |
| | UNLESS SPECIFICALLY PERMITTED IN 400.10, FLEXIBLE |
| | CABLES, FLEXIBLE CORD SETS, AND POWER SUPPLY CORDS |
| | SHALL NOT BE USED FOR THE FOLLOWING: |
| | (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A |
| | STRUCTURE. |
| | |
| | 3) PLEASE PROVIDE AN ELECTRICAL FLOOR/SITE PLAN |
| | LOCATING ALL EQUIPMENT SHOWN IN SCHEMATIC DRAWING. FBC |
| | 107.2 |
| | |
| | 4) PLAN DETAILS AN NEW 225 AMP ELECTRIC PANEL. NOTES |
| | CONTAINED IN THIS PLAN INDICATE THIS PANEL TO BE |
| | INSTALLED BY OTHERS. PLEASE PROVIDE THE APPLICABLE |
| | PERMIT APPLICATION AND PLANS FOR NEW PANEL. FBC 107.2 |
| | |
| | 5) PLEASE PROVIDE DETAILS OF WIRE METHODS USED FOR ALL |
| | WIRING. NEC 110.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |