| Plan Review Notes For Permit 23040946 |
| Permit Number |
23040946 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-06-08 08:00:17 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | | | | 2.) FBC 603.1,(ITEM 2, EXCEPTION 2), PROVIDE THE FLAME | | | SPREAD TEST REPORT FOR FLOORING UNDERLAYMENT. ALLOWABLE | | | MATERIALS IN NON COMBUSTIBLE BUILDINGS, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. | | | PLEASE IDENTIFY THE UNDERLAYMENT THAT YOU ARE PROPOSING | | | TO USE AS THERE ARE (2) DIFFERENT UNDERLAYMENTS | | | (PROFLEX LV200) & (PROTECTO WRAP WHISPERMAT CS). | | | PLEASE CONFIRM THAT YOU WOULD LIKE TO REMOVE PROTECTO | | | WRAP WHISPER MAT CS FROM THE APPLICATION. | | | | | | 3.) CITY OF WPB AMENDMENTS TO FBC B 107.2.1, PROVIDE | | | THE CONTRACTOR'S SIGNATURE ON ALL SUBMITTED PLAN SHEETS | | | BY THE CONTRACTOR. | | | |
|