Plan Review Notes
Plan Review Notes For Permit 23040938
Permit Number 23040938
Review Stop B
Sequence Number 1
Notes
Date Text
2023-04-26 09:21:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. SUBMITTED PRODUCT APPROVAL FL10497-R8 HAS BEEN
 REVISED TO FL10497-R10. PLEASE PROVIDE THE FOLLOWING:
 INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-4 AND
 INSTALLATION INSTRUCTIONS FOR SYSTEM USED. FLORIDA DBPR
 PRODUCT APPROVAL FL10497-R8 SYSTEM NO. W-156 DO NOT
 MEET THE MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF
 -108.17 FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM
 THAT MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS
 FOR EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED
 ENGINEERED NAILING CALCULATIONS WITH AN APPROVED
 SYSTEM. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 AS PER RULE 61G20-3.
 2. SUBMITTED PRODUCT APPROVAL FL4595-R6 HAS BEEN
 REVISED TO FL4595-R8. PLEASE PROVIDE THE FOLLOWING:
 INCLUDE COVER PAGE, EVALUATION REPORT PAGES 1-5. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS
 AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT
 APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING
 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL4595.14-R6 MAXIMUM DESIGN PRESSURE -116 PSF.
 DO NOT MEET THE MINIMUM ZONE 3 DESIGN PRESSURE
 REQUIREMENT OF -121 FOR EXPOSURE CATEGORY C AREAS WITH
 A GABLE ROOF; ROOF SLOPES 2/12-4/12 MEAN ROOF HEIGHT UP
 TO 15 FT. SELECT SYSTEM THAT MEETS OR EXCEEDS THIS
 REQUIREMENT. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING.
 4. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND INCLUDE ROOF SLOPE(S), MEAN ROOF
 HEIGHT(S). FLAT/LOW SLOPE ROOFS MUST SHOW POSITIVE
 DRAINAGE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  