| Plan Review Notes For Permit 23040933 |
| Permit Number |
23040933 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2023-06-14 14:20:01 | ROOFING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE ENGINEERING FROM SANDRA PUERTA AR - NEEDS TO | | | SHOW THE ATTACHMENT FOR ROOF WIND ZONE -1', 1, 2 AND 3 | | | (ALL 4 WIND ZONES). | | | | | | THE WIND PRESSURES FROM THE COUNTY SHOW 4 WIND ZONES - | | | 1',1, 2, 3 | | | | | | THERE ARE 4 NEW ROOF ZONES. SEE FIGURE | | | R301.2(7)FBC-RESIDENTIAL. | | | | | | | | | |
|