| Plan Review Notes For Permit 23040931 |
| Permit Number |
23040931 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-12 13:38:07 | CANOPY | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWINGS ARE NOT CLEAR - PLEASE DESCRIBE THE | | | BUILDING - POLE BARN WITH 2 SIDE WALLS? | | | | | | 2) PLEASE SHOW THE STRUCTURE LOCATION ON A SURVEY - | | | SHOWING THE BLDG, SETBACKS FROM THE PROPERTY LINES AND | | | ADJACENT BUILDINGS. | | | | | | 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) PRODUCT APPROVAL LISTED ON | | | THE DRAWINGS FOR THE WALL PANELS AND THE ROOF PANELS. | | | | | | 4) DRAWING SHEET 5 SHOWS WALL PANELS AT 140MPH - | | | STRUCTURES IN RISK CATEGORY I WILL NEED TO BE DESIGNED | | | FOR 150MPH WIND SPEEDS PER FBC WPB SECTION 120 | | | | | | 5) JOB COST APPEARS TO BE LOW - JOB COST ON THE | | | BUILDING PERMIT APPLICATION NEEDS TO INCLUDE ALL | | | MATERIALS AND LABOR - PLEASE REVISE THE BUILDING PERMIT | | | APPLICATION IF NEEDED. |
|