| Date |
Text |
| 2023-04-19 10:57:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE G 1.0 PLAN SHEET OF NO |
| | FIRE SPRINKLER SYSTEM; HOWEVER, THERE IS AN INDICATION |
| | OF A POST INDICATOR VALVE RIGHT OUTSIDE THE REAR OF THE |
| | UNIT. |
| | |
| | THIS VALVE WOULD INDICATE THE PRESENCE OF A FIRE |
| | SPRINKLER SYSTEM. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | PLEASE REVIEW AND CONFIMR THE PRESENCE OF FIRE |
| | SPRINKLER PROTECTION. |
| | |
| | IF PRESENT, THE FIRE SPRINKLER & FIRE ALARM SYSTEMS |
| | SHALL BE MAINTAINED THROUGHOUT DEMO & CONSTRUCTION |
| | PERIODS |
| | |
| | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING |
| | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP |
| | DRAWINGS. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF THE LIFE SAFETY PLAN. |
| | |
| | |
| | 2) THERE IS AN INDICATION OF THE G 1.0 PLAN SHEET OF A |
| | FIRE ALARM SYSTEM, BUT NO INDICATION OF FA WORK BEING |
| | COMPLETED. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | THE FIRE ALARM SYSTEMS SHALL BE MAINTAINED THROUGHOUT |
| | DEMO & CONSTRUCTION PERIODS |
| | |
| | ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE |
| | DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| | |
| | PROVIDE AN APPLICABLE NOTE OF THE LIFE SAFETY PLAN AND |
| | ELECTRICAL PLAN |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |