| 2023-05-02 18:04:55 | RESIDENTIAL (R2)BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23040885 |
| | 300 S AUSTRALIAN AVE # 1119 |
| | |
| | 1- PROVIDE FLOOR PLAN SHOWING AREAS TO HAVE NEW |
| | FLOORING. AND, SPECIFY FLOOR AREA OF EACH ROOM. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 2- FINISH FLOOR MATERIAL TO BE INSTALLED IS NOT CLEAR. |
| | PERMIT APPLICATION STATES " REMOVE CARPETS AND REPLACE |
| | WITH VINYL FLOORING". CONTRACTOR UPLOADED |
| | SPECIFICATIONS FOR LAMINATED WOOD FLOORS. CONTRACTOR TO |
| | REVISE SCOPE OF WORK ON PERMIT APPLICATION TO MATCH |
| | SPECIFICATIONS SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- CONTRACTOR UPLOADED SPECIFICATIONS FOR LAMINATED |
| | PLANKS WALL MOUNTING . PROVIDE FLOOR PLAN SHOWING AREAS |
| | TO HAVE LAMINATED WALL PLANKS AND PROVIDE DETAILS |
| | SHOWING WALLS AREAS TO BE COVERED. FULL WALL, PARTIAL |
| | WALL, ETC.? SPECIFY FLOOR AREA OF EACH ROOM. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES (IF ANY) AS REQUIRED BY SEC. 109.3 |
| | CITY AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS |
| | OR PROVIDE COMPLETE COST BREAKDOWN INCLUDING DESIGN |
| | PROFESSIONAL FEES (IF ANY). |
| | |
| | 5- FLOORING SOUND INSULATION MATERIAL: |
| | (A)PROFLEX SUPER SIM-90 COPY OF THE FLAME SPREAD INDEX |
| | AND SMOKE DEVELOPED INDEX TEST SUBMITTED IS FOR TILE |
| | INSTALLATION. CONTRACTOR NEEDS TO SUBMIT COPY OF TEST |
| | FOR LAMINATED WOOD FLOOR. (NOTE: UNDERLAYMENT PRODUCT |
| | TO MATCH UNDERLAYMENT USED ON REQUIRED TESTS BELOW). |
| | SEC. 720.1 AND 720.2 OF FBC 7TH EDITION (2020). |
| | |
| | (B)PROFLEX MSC-90 COPY OF THE SOUND TRANSMISSION CLASS |
| | (STC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| | NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| | SEC. 1207.2 OF FBC 7TH EDITION (2020). |
| | NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| | SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| | |
| | (C)PROFLEX MSC-90 COPY OF THE IMPACT INSULATION CLASS |
| | (IIC) SUBMITTED IS FOR TILE INSTALLATION. CONTRACTOR |
| | NEEDS TO SUBMIT COPY OF TEST FOR LAMINATED WOOD FLOOR. |
| | SEC. 1207.3 OF FBC 7TH EDITION (2020). |
| | NOTE: THIS BUILDING DOESN'T HAVE 8" CONCRETE SLAB. |
| | SUBMIT TEST FOR 7" CONCRETE SLAB OR LESS. |
| | |
| | |
| | NOTE: TEST SAMPLES TO MATCH BUILDING FLOOR CONSTRUCTION |
| | (WOOD TRUSSES/JOISTS OR CONCRETE SLAB) AND PROPOSED |
| | FLOOR FINISH. |
| | NOTE: THERE ARE TESTS FOR 6" OR 8" CONCRETE SLABS WITH |
| | OR WITHOUT ACOUSTICAL CEILING. TYPICALLY THERE ARE NOT |
| | SUSPENDED ACOUSTICAL CEILINGS IN THESE BUILDINGS. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT). |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |