Plan Review Notes
Plan Review Notes For Permit 23040839
Permit Number 23040839
Review Stop G
Sequence Number 2
Notes
Date Text
2023-05-22 07:38:501ST GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. NOT ADDRESSED CORRECTLY - SEE NOTES BELOW -- 2020
 FRC G2413.3 (402.3) - THE LINE FROM THE METER TO THE
 1ST TEE APPEARS TO BE UNDERSIZED. ACCORDING TO TABLE
 402.4(22)-250 FT, YOU ARE UNDERSIZED. 1 1/4 CAN ONLY
 HANDLE 2,040K BTU AND YOU ARE RUNNING 2,651K BTU.
  
 NOTES: YOU ARE STATING THAT THE LONGEST RUN IS 110'?
 THE LONGEST RUN IS MEASURED FROM THE SUPPLY TO THE
 FURTHEST FIXTURE. THIS WOULD BE 220'. THE NEXT LINE ON
 THE GAS CHART IS 250'. ACCORDING TO THAT LINE IN THE
 TABLE, YOU ARE UNDERSIZED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  