| Notes |
| Date |
Text |
| 2023-04-21 07:11:21 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23040812 | | | 4/21/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WILKINS 975XL RPZ | | | DOES NOT SHOW THAT THE DEVICE MEETS THE REQUIREMENTS OF | | | NSF/ANSI/CAN 61 (0.25% MAX WEIGHTED AVERAGE LEAD | | | CONTENT). SUBMIT SPECS FOR THE 975XL2 WHICH MEETS THE | | | REQUIREMENTS- WPB UTILITIES CROSS-CONNECTION MANUAL. | | | | | | 605.2.1 LEAD CONTENT OF DRINKING WATER PIPE AND | | | FITTINGS. | | | PIPE, PIPE FITTINGS, JOINTS, VALVES, FAUCETS AND | | | FIXTURE FITTINGS UTILIZED TO SUPPLY WATER FOR DRINKING | | | OR COOKING PURPOSES SHALL COMPLY WITH NSF 372 AND SHALL | | | HAVE A WEIGHTED AVERAGE LEAD CONTENT OF 0.25 PERCENT OR | | | LESS. | | | | | | 2) PLEASE MARK THE EXACT LOCATION OF THE BACKFLOW | | | PREVENTER ON THE SITE PLAN- SEC. 107.2.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|