2023-05-01 10:18:531ST REVIEW FMC
 PERMIT: 23040797
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A COMPLETE SUBMITTAL FOR THIS GENERATOR
 INCLUDING THE TYPE OF FUEL AND ANY PIPING THAT WILL BE
 USED TO BRING THE FUEL FROM THE FUEL TRUCK TO THE
 GENERATOR TANK. INCLUDE THE TANK AND THE FUEL FILL
 STATION INFORMATION. THIS INFORMATION SHOULD ALSO
 INCLUDE THE GENERATOR MUFFLER WITH A DETAIL DRAWING
 SHOWING THE INSTALLATION OF THE EXHAUST TERMINATION.
 FBC 107.3.5
  
 2) THE APARTMENT BESIDE OF THIS GENERATOR ROOM SHOWS 2
 WINDOWS IN THE BEDROOM WHICH IS NEXT TO THE GENERATOR
 EXHAUST LOCATION. PLEASE SHOW THAT THESE WINDOWS ARE
 NOT OPERABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  