| 2023-04-17 16:23:06 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II/INSPECTOR |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | FBC B 107.2.1, PROVIDE MORE INFORMATION. PLEASE CLARIFY |
| | THE COMPLETE SCOPE OF WORK FOR THIS PROJECT AS IT |
| | APPEARS THAT NEW PLAN SHEETS WILL NEED TO INCLUDE THE |
| | FOLLOWING: |
| | |
| | FLOOR PLAN SHOWING THE EXISTING AREA OF CONSTRUCTION |
| | AND THE PROPOSED CONSTRUCTION AT THAT AREA INCLUDING |
| | NEW WINDOW/DOOR LOCATIONS, PLAN SHEETS SHOWING THE |
| | CONNECTION DETAILS FOR ALL OF THE PROPOSED NEW TRUSS TO |
| | THE EXISTING TRUSS AND EXISTING STRUCTURAL MEMBERS, |
| | PLAN SHEETS WITH DETAILS FOR NEW STRUCTURAL MEMBERS |
| | INCLUDING BEAMS/COLUMNS & WALLS, & LOCATION WITH |
| | DIMENSIONS OF NEW WINDOWS TO BE INSTALLED. |
| | |
| | THESE DETAILS AND CALCULATIONS ARE TYPICALLY PUT |
| | TOGETHER BY A DESIGN PROFESSIONAL AS THEY NEED TO SHOW |
| | THE LOAD CAPACITIES (INCLUDING UPLIFT CAPACITIES) AT |
| | THE CONNECTION POINTS. |
| | ALL SUBMITTALS BY A DESIGN PROFESSIONAL (ARCHITECT OR |
| | ENGINEER) WILL NEED TO BE SIGNED AND SEALED BY THAT |
| | DESIGN PROFESSIONAL. |
| | |
| | ALSO, FOR ENCLOSING AN EXISTING OPEN PATIO AND |
| | INCREASING WHAT IS CONSIDERED THE LIVING SPACE, ENERGY |
| | CALCULATIONS ARE REQUIRED MEANING THAT ELECTRICAL AND |
| | MECHANICAL PERMITS WILL BE NEEDED. |