Plan Review Notes
Plan Review Notes For Permit 23040706
Permit Number 23040706
Review Stop G
Sequence Number 1
Notes
Date Text
2023-04-14 11:16:121ST REVIEW FBC-2020 RES. GAS
 PERMIT- 23040706
 4/14/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SURVEY APPEARS TO SHOW THE PE LINE RUNNING
 UNDERNEATH THE BUILDING WHICH IS PROHIBITED REGARDLESS
 OF THE PIPING BEING RUN IN A CONDUIT- SEE SEC.
 G2415.17.1 FBC RES. PLEASE NOTE CSST PIPING RATED FOR
 UNDERGROUND INSTALLATION IS ALLOWED AND IS USED
 FREQUENTLY UNDER THE BUILDING.
  
 2) GAS RISER: APPROVED GAS PLAN UNDER PERMITS 15040343
 AND 15120040 SHOW A 180,000 BTU TANKLESS WATER HEATER
 SUPPLIED BY A ??-INCH GALVANIZED LINE. IS THIS WATER
 HEATER STILL IN USE, REMOVED OR RELOCATED?
  
 A) I WAS UNABLE TO LOCATE A PERMIT FOR THE FIREPLACE.
 PLEASE PROVIDE COMBUSTION AIR CALCULATIONS AND A
 VENTING DIAGRAM- SECS. G2407.1, G2427.1 FBC RES. IF
 USING THE STANDARD INDOOR AIR METHOD FOR COMBUSTION,
 THE CALCULATION I 50 CU.FT. PER 1000 BTU- SEC.
 G2407.5.1 FBC RES. THE VENT DIAGRAM SHALL SHOW THE TYPE
 AND SIZE OF VENT FLUE, VENT RUN LENGTH AND TERMINATION
 LOCATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  