| 2023-04-13 15:47:37 | RESIDENTIAL(R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #23040527 |
| | 4739 PALMBROOKE CIR |
| | |
| | NOTE: |
| | LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| | SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| | COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| | THE FLORIDA BUILDING CODE. |
| | |
| | 1- DESIGN PRESSURES ON SKYLIGHT NOA 18-0307.10 |
| | SUBMITTED ARE LOW (-75.0PSF). |
| | BASED ON TABLE R301.2(2) AND TABLE R301.2(3) |
| | FBC-RESIDENTIAL THE DESIGN PRESSURES ARE -77.76PSF FOR |
| | 25FEET MEAN ROOF HEIGHT AND ROOF PITCH 5.5:12. THE |
| | SKYLIGHT IS LOCATED IN ROOF ZONE 2R. NEED TO PROVIDE |
| | PRODUCT APPROVAL THAT MEETS OR EXCEEDS THESE DESIGN |
| | PRESSURES OR PROVIDE SITE SPECIFIC SIGNED CALCULATIONS |
| | IF CONTRACTOR BELIEVES THE DESIGN PRESSURES ARE LOWER. |
| | SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |