Plan Review Notes
Plan Review Notes For Permit 23040476
Permit Number 23040476
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2023-04-19 09:59:02FIRE PROVISO:
  
  
 1) THERE IS AN INDICATION OF EXIT ACCESS PASSING
 THROUGH A STOREOOM.
  
 PER NFPA 101 CH 36
  
 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE
 OCCUPANCIES
 THAT ARE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND
 EXIT ACCESS IN ALL
 CLASS C MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO
 PASS THROUGH
 STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
  
 (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED THROUGH
 THE STOREROOM.
  
 (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
  
 (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN 44 IN.
 (1120 MM) WIDE.
  
 (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT,
 AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
  
 A DELINEATED LINED PATH SHALL BE PLACED/TAPED/PAINTED
 ON THE FLOOR TO HELP
 ENSURE THE EXIT PATH IS MAINTAINED AND UNOBSTRUCTED.
  
  
 2) ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND
 EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS
 FOR CODE COMPLIANT COVERAGE
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  