| Plan Review Notes For Permit 23040476 |
| Permit Number |
23040476 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-19 09:59:02 | FIRE PROVISO: | | | | | | | | | 1) THERE IS AN INDICATION OF EXIT ACCESS PASSING | | | THROUGH A STOREOOM. | | | | | | PER NFPA 101 CH 36 | | | | | | 36.2.5.11 EXIT ACCESS IN CLASS A AND CLASS B MERCANTILE | | | OCCUPANCIES | | | THAT ARE PROTECTED THROUGHOUT BY AN APPROVED, | | | SUPERVISED AUTOMATIC | | | SPRINKLER SYSTEM IN ACCORDANCE WITH 9.7.1.1(1), AND | | | EXIT ACCESS IN ALL | | | CLASS C MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO | | | PASS THROUGH | | | STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING | | | CONDITIONS ARE MET: | | | | | | (1) NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE | | | PROVIDED THROUGH | | | THE STOREROOM. | | | | | | (2) THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING. | | | | | | (3) THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT | | | LESS THAN 44 IN. | | | (1120 MM) WIDE. | | | | | | (4) THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE | | | DEFINED, DIRECT, | | | AND CONTINUOUSLY MAINTAINED IN AN UNOBSTRUCTED | | | CONDITION. | | | | | | A DELINEATED LINED PATH SHALL BE PLACED/TAPED/PAINTED | | | ON THE FLOOR TO HELP | | | ENSURE THE EXIT PATH IS MAINTAINED AND UNOBSTRUCTED. | | | | | | | | | 2) ANY REMOVAL OR CONSTRUCTION OF WALLS REQUIRES AND | | | EVALUATION OF THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS | | | FOR CODE COMPLIANT COVERAGE | | | | | | THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING | | | DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|