2023-04-21 11:52:26FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW
  
 1. PROVIDE INFORMATION OF THE FOLLOWING EXISTING
 FEEDERS:
 A. FROM THE 208/120V 400AS/400AF DISCONNECT TO THE
 EXIST. PANEL A
 B. FROM EXIST. PANEL A TO EXIST. PANEL B
 FBC 107.3.5.3
  
 NOTE: LOW VOLTAGE NEEDS A SEPARATE PERMIT APPLICATION
  
 END OF COMMENTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  