Plan Review Notes
Plan Review Notes For Permit 23040456
Permit Number 23040456
Review Stop P
Sequence Number 1
Notes
Date Text
2023-05-08 07:24:361ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 1003.3.1 - IT APPEARS THAT A GREASE TRAP IS
 REQUIRED. PLEASE DETAIL AND UPDATE THE RISER TO SHOW
 ALL FIXTURES THAT WILL HAVE F.O.G. WASTE WILL DISCHARGE
 INTO AN INTERCEPTOR.
  
 2. 2020 FPC 1002.1 - THE "HUB DRAIN" AT THE FRONT OF
 THE DISPLAY COUNTER CANNOT DISCHARGE INTO THE RISER OF
 THE NEARBY FLOOR DRAIN. EACH FIXTURE MUST BE SEPARATELY
 TRAPPED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  