Plan Review Notes
Plan Review Notes For Permit 23040447
Permit Number 23040447
Review Stop E
Sequence Number 1
Notes
Date Text
2023-04-24 11:21:40ELECTRIC REVIEW FAILED
  
 1) IT APPEARS THIS IS A REMOTE STRUCTURE. PLEASE DETAIL
 HOW THE ELECTRIC FEEDING THIS STRUCTURE IS IN
 COMPLIANCE WITH NEC 225.30, NUMBER OF SUPPLIES.IF AN
 ELECTRIC PANEL IS LOCATED IN THE REMOTE STRUCTURE
 PLEASE DETAIL THE REQUIRE GROUNDING ELECTRODE SYSTEM AS
 REQUIRED PER NEC 250.32
  
 A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT
  
  
 2) PLEASE LOCATE ALL ELECTRICAL EQUIPMENT ON FLOOR
 PLAN, I.E. AIR HANDLER/AIR CONDENSER/ DISCONNECTS,
 WATER HEATERS, ELECTRIC PANEL, ELECTRIC METER, ENSURE
 CLEARANCES AS REQUIRED. PLEASE INDICATE AND DISTINGUISH
 BETWEEN NEW AND EXISTING EQUIPMENT NEC 110.26 FBC 107.2
  
 3) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM DETAILING
 ALL ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND
 OVERCURRENT PROTECTION SIZES. NEC 215.5 NEC 240.4 FBC
 107.2
  
 4) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION FOR ALL
 ELECTRIC LOADS SERVED. NEC 220.40 OR NEC 220.80
  
 5) PLEASE INDICATE USE OF SPACE. WILL THIS SPACE BE
 USED AS A SLEEPING AREA? THIS SPACE MAY REQUIRE SMOKE
 ALARMS AS REQUIRED PER FBC R 314
  
 6) PLEASE DETAIL COMPLIANCE WITH NEC 210.8 AND NEC
 210.12 FOR GROUND FAULT AND ARC FAULT PROTECTION.
  
 7) PLEASE DETAIL THE REQUIRED OUTDOOR RECEPTACLES AS
 REQUIRED PER NEC 210.52(E)
  
 8) PLEASE DETAIL THE REQUIRED OUTDOOR LIGHTING OUTLETS
 AS REQUIRED PER NEC 210.70(A)(2)(2)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  