| 2023-04-24 08:36:47 | ELECTRIC REVIEW FAILED |
| | |
| | 1) PLEASE LOCATE ALL ELECTRICAL EQUIPMENT ON FLOOR |
| | PLAN, I.E. AIR HANDLER/AIR CONDENSER/ DISCONNECTS, |
| | WATER HEATERS, ELECTRIC PANEL, ELECTRIC METER, ENSURE |
| | CLEARANCES AS REQUIRED. PLEASE INDICATE AND DISTINGUISH |
| | BETWEEN NEW AND EXISTING EQUIPMENT NEC 110.26 FBC 107.2 |
| | |
| | 2) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM DETAILING |
| | ALL ELECTRICAL EQUIPMENT, CONDUIT, CONDUCTOR AND |
| | OVERCURRENT PROTECTION SIZES. PLEASE INDICATE AND |
| | DISTINGUISH BETWEEN NEW AND EXISTING EQUIPMENT NEC |
| | 215.5 NEC 240.4 FBC 107.2 |
| | |
| | 3) PLEASE PROVIDE AN ELECTRIC LOAD CALCULATION FOR ALL |
| | ELECTRIC LOADS SERVED. NEC 220.40 OR NEC 220.80 |
| | |
| | 4) PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS WATER |
| | HEATER. ENSURE TO INCATE SPECIFIC MODEL NUMBER AND |
| | ELECTRICAL WIRING REQUIRED. FBC 107.2, NEC 220.40, NEC |
| | 24O.4 |
| | |
| | 5) PLAN SPECIFICALLY INDICATES NEW RECESSED LIGHTING, |
| | HOWEVER, ADDITIONAL ELECTRICAL WIRING IS INDICATED ON |
| | PLAN SUBMITTED AND DOES NOT DETAIL WHETHER THIS WIRING |
| | IS NEW OR EXISTING. PLEASE DETAIL ALL WIRING ON |
| | SUBMITTED PLANS AS EITHER NEW OR EXISTING. FBC.107.2 |
| | |
| | 6) PLEASE DETAIL ON ELECTRICAL PLAN THE REQUIRED |
| | OUTDOOR RECEPTACLES IN ACCORDANCE WITH NEC 210.52(E) |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |