Plan Review Notes
Plan Review Notes For Permit 23040389
Permit Number 23040389
Review Stop P
Sequence Number 1
Notes
Date Text
2023-04-26 10:08:151ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.3.5.3 (12) - MISSING FROM THE
 PLUMBING RISER IS THE HALL BATH
  
 2. 2020 FPC P3104.4 - BATH 2 - THE VENT CANNOT BE
 HORIZONTAL BELOW THE FLOOD RIM OF THE FIXTURE SERVED.
  
 3. 2020 FRC P3108.1 - THE HALL BATH DRAIN
 CONFIGURATION, ONLY SHOWN ON THE FLOOR PLAN, IS NOT TO
 CODE. THE FIXTURES CANNOT BE VENTED OFF OF THE MAIN
 BRANCH.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved