| Plan Review Notes For Permit 23040367 |
| Permit Number |
23040367 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-19 10:35:39 | 1ST PLUMBING REVIEW | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FPC 403.1.1 - PLEASE SHOW THE OCCUPANT LOAD AND | | | USE OF EACH SPACE TO SHOW COMPLIANCE WITH THE MINIMUM | | | NUMBER OF PLUMBING FIXTURES REQURIED FOR THE USE. | | | | | | 2. 2020 FPC 403.1.1 - SHOW THE OCCUPANT LOAD AND | | | DETERMINE IF YOU NEED TO PROVIDE A DRINKING FOUNTAIN OR | | | THE EXEMPTION FROM ONE. | | | | | | 3. 2020 FPC 403.1.1 - SHOW THE REQUIRED SERVICE SINK OR | | | THE THAT YOU QUALIFY FOR THE EXCEPTION. | | | | | | 4. 2020 FPC 607.1 - SHOW THE REQUIRED HOT WATER. ALSO | | | INCLUDE DETAILS THAT SHOW COMPLIANCE WITH 607.1.1/613.1 | | | AS WELL AS 607.1.2/419.5. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | |
|