2023-04-19 10:35:391ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - PLEASE SHOW THE OCCUPANT LOAD AND
 USE OF EACH SPACE TO SHOW COMPLIANCE WITH THE MINIMUM
 NUMBER OF PLUMBING FIXTURES REQURIED FOR THE USE.
  
 2. 2020 FPC 403.1.1 - SHOW THE OCCUPANT LOAD AND
 DETERMINE IF YOU NEED TO PROVIDE A DRINKING FOUNTAIN OR
 THE EXEMPTION FROM ONE.
  
 3. 2020 FPC 403.1.1 - SHOW THE REQUIRED SERVICE SINK OR
 THE THAT YOU QUALIFY FOR THE EXCEPTION.
  
 4. 2020 FPC 607.1 - SHOW THE REQUIRED HOT WATER. ALSO
 INCLUDE DETAILS THAT SHOW COMPLIANCE WITH 607.1.1/613.1
 AS WELL AS 607.1.2/419.5.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  