2023-07-17 16:07:15WEST PALM BEACH DEVELOPMENT SERVICES
 BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W.P.B. REVISION: 23040360
 W. P. B. PERMIT: 21091210
 ADD:1230 PALM BEACH LAKES BLVD
 CONT: HJB CONSTRUCTION
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JULY17TH/ 2023
 ACTION: DENIED
 NOTICE: NO BAR JOIST SUBMITAL PROVDED!!!!!!!
  
 1) 3RD REQUEST. THE SUBMITTED MIAMI-NOA 19-0220.03 HAS
 NO VALUE FOR TESTING FOR WIND, THIS NOA SHOWS THAT THE
 PRODUCTS LISTED ONLY MEET THE REQUIREMENTS FOR ASTM AND
 TAS REQUIREMENTS. PLEASE GO BACK TO THE MIAMI-DADE
 WEBSITE AND VIEW NOA 18-0501.13 PICK A SUB-SYSTEM FOR
 TPO ON METAL DECK WITH INSULATION CIRCLE THE SUB-SYSTEM
 AND SEE IF LIMITATION 7 OR LIMITATION 9 APPLIES.
 SYSTEMS WITH LIMITATION # 7 CAN HAVE ENHANCED FASTENING
 FOR ZONES 2 & 3. FOR ALL ROOFING PRODUCTS PLEASE
 IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED
 PRESSURES FOR ROOF ZONE # 1. REVIEW THE PRODUCT
 APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED
 FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL BE
 INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 2ND REQUEST. SUBMITTED THIS REVISION ARE VARIOUS
 DOCUMENTS FOR A JOHN MANVILLE TPO-60 MIL BUT NO PRODUCT
 APPROVAL SUBMITTED, EITHER MIAMI-DADE NOA OR FLORIDA
 APPROVAL SHOULD BE SUBMITTED. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 2)ARCHITECT STAMPED APPROVAL ON 7 SHEET ASSEMBLY LETTER
 FROM JOHNS MANVILLE WITHOUT REVIEW OF THE REQUIRED
 PRODUCT APPROVAL WITH SUB-SYSTEMS HIGHLIGHTED,
 PRESSURES, JOIST SPACING, DECK GAUGE AND LIMITATIONS.
 .
  
 3) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 4) COMPLIED, ROOF PRESSURES ON SHEET S0 PERMIT 21091210
 SECTION 4-L PRESSURES ON DECK..
  
 5) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT
 REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  