| Plan Review Notes For Permit 23040318 |
| Permit Number |
23040318 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-05-25 12:12:20 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 23040318 | | | 5/25/23 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P-001: PLEASE PROVIDE SANITARY AND WATER RISER | | | DRAWINGS AS REQUIRED BY SEC. 107.3.5.1.3 WPB. RISER | | | DRAWINGS WERE INCLUDED ON PLANS UNDER 23040315, | | | 23040316 & 23040317 AND INCLUDED PIPING CONNECTIONS TO | | | THE WATER HEATERS. | | | | | | 2) THE PLUMBING PLANS- SHEETS P-001, P-101, P-102, | | | P-201, P-501, & P-901 ARE NOT DIGITALLY SIGNED AND | | | SEALED BY THE ENGINEER OF RECORD AND CANNOT BE | | | APPROVED- FL. STATUTE 471.025 AND SEC. 61G15-23.005 | | | FLORIDA ADMINISTRATIVE CODE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|