2023-04-26 16:29:53SOLAR PANELS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE PERCENTAGE OF THE SOLAR PANELS TO BE
 INSTALLED ON THE ENTIRE ROOF SQUARE FOOTAGE - FBC
 R324.6.2 SETBACK AT RIDGE.
 FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33
 PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS THAN
 AN 18-INCH (457 MM) CLEAR SETBACK IS REQUIRED ON BOTH
 SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS
 OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL
 ROOF AREA, NOT LESS THAN A 36-INCH (914 MM) CLEAR
 SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL
 RIDGE.
  