| Plan Review Notes For Permit 23040295 |
| Permit Number |
23040295 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2023-04-26 16:29:53 | SOLAR PANELS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE PERCENTAGE OF THE SOLAR PANELS TO BE | | | INSTALLED ON THE ENTIRE ROOF SQUARE FOOTAGE - FBC | | | R324.6.2 SETBACK AT RIDGE. | | | FOR PHOTOVOLTAIC ARRAYS OCCUPYING NOT MORE THAN 33 | | | PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, NOT LESS THAN | | | AN 18-INCH (457 MM) CLEAR SETBACK IS REQUIRED ON BOTH | | | SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC ARRAYS | | | OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL | | | ROOF AREA, NOT LESS THAN A 36-INCH (914 MM) CLEAR | | | SETBACK IS REQUIRED ON BOTH SIDES OF A HORIZONTAL | | | RIDGE. | | | |
|