| 2023-05-22 16:16:23 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 23040294 |
| | 5/16/23 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. THESE 1ST REVIEW COMMENTS |
| | WERE INSERTED UNDER THE 2ND REVIEW DUE TO A LOCKUP IN |
| | THE SOFTWARE. |
| | |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE POTABLE WATER |
| | BACKFLOW PREVENTER AND THE SAND/OIL INTERCEPTOR. AT A |
| | MINIMUM, THE PERMIT APPLICATIONS FOR EACH SHALL BE |
| | SUBMITTED PRIOR TO MAIN PLUMBING PLAN APPROVAL. IF |
| | CONTRACTORS ARE NOT CURRENTLY SELECTED FOR EACH |
| | INSTALLATION, PERMIT APPLICATIONS CAN BE SUBMITTED TBD |
| | (TO BE DETERMINED). EACH COMPLETED APPLICATION SHALL BE |
| | EMAILED TO [email protected] . YOU WILL THEN |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATIONS ARE REQUIRED AT THIS TIME. WE RECOMMEND |
| | THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. |
| | AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA |
| | EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 2) SHEETS P001 & P201B: THE SK-3 SINKS IN THE SERVICE |
| | FLOOR AREA ARE LISTED AS ADA COMPLIANT IN THE SCHEDULE. |
| | PLEASE PROVIDE ACCESSIBILITY DETAILS FOR THE SINKS |
| | INCLUDING CLEAR FLOOR SPACES, SINK HEIGHTS, AND KNEE |
| | AND TOE CLEARANCES- SEC. 606.2 FBC ACC. |
| | |
| | 3) P201B, P501: THE SK-3 SINKS ON THE NORTH SIDE OF THE |
| | SERVICE FLOOR AREA ARE DRAINING INTO THE SANITARY |
| | HOWEVER THE SK-3 SINK FLOOR DRAINS ON THE SOUTH SIDE |
| | ARE DRAINING INTO THE SAND/OIL INTERCEPTOR. REFER TO |
| | SEC. 1003.4 FBC P AND CLARIFY THE PURPOSES OF THE SINKS |
| | AND THE CONTENT OF DRAINAGE FROM EACH. |
| | |
| | 4) P201A: PLEASE PROVIDE AN ENLARGED PLUMBING DETAIL |
| | FOR THE ELEVATOR SUMP PUMP AND PIT IN ACCORDANCE WITH |
| | SEC. 712.1- 712.3.5 FBC P. PLEASE SEE SEC. 3002.9 FBC B |
| | AND SHOW THE PUMP DISCHARGE PIPE WILL INDIRECTLY |
| | CONNECTED TO THE SANITARY DRAINAGE SYSTEM. |
| | |
| | 5) P301B, P401: PLEASE SHOW THE LOCATION OF THE MAIN |
| | WATER SHUTOFF VALVE FOR THE CARWASH- SEC. 606.1 FBC P. |
| | |
| | 6) P001 & P401: PROVIDE AN EQUIPMENT SCHEDULE FOR THE |
| | RPZ BACKFLOW PREVENTER AT THE CAR WASH SUPPLY LINE- |
| | TABLE 608.1 FBC P. |
| | |
| | 7) P501: THE VENT SYSTEM FOR THE MAIN RESTROOMS APPEARS |
| | TO BE A CLOSED LOOP WITH NO MEANS OF PROVIDING AIR FOR |
| | CIRCULATION. PLEASE PROVIDE A VENT FOR THE SYSTEM THAT |
| | EXTENDS TO OPEN AIR OR AN AAV- SEC. 905.1 FBC P. |
| | |
| | 8) P502: SHOW THE MEANS OF PROVIDING TEMPERED WATER |
| | DELIVERY FROM THE PUBLIC LAVATORIES- SEC. 419.5 FBC P. |
| | PLEASE NOTE TEMPERED WATER MIXING VALVES SHALL CONFORM |
| | TO ASSE 1070- SEC. 607.1.2 FBC P. |
| | |
| | 9) P701: SHOW THE HOT WATER RECIRCULATION LINE WILL |
| | ALSO MAKE CONNECTION TO THE COLD WATER INLET PIPE OR |
| | THE HOT WATER RETURN CONNECTION OF THE THERMOSTATIC |
| | MIXING VALVE- SEC. 607.2.2 FBC P. PLEASE INCLUDE THE |
| | TMV IN THE EQUIPMENT SCHEDULE ON P001. |
| | |
| | 10) P701: CONCERNING THE SAND/OIL INTERCEPTOR UNDER |
| | SEPARATE PERMIT PLEASE SUBMIT MANUFACTURER???S |
| | SPECIFICATIONS INDICATING THE UNIT IS LISTED OR |
| | LABELED. IF NOT LISTED AND LABELED THE UNIT IN THE |
| | DETAIL SHALL HAVE AN 18-INCH WATER SEAL AT THE OUTLET |
| | OPENING AND SHALL HAVE A CAPACITY OF NOT LESS THAN 6 |
| | CUBIC FEET FOR THE FIRST 100 SQUARE FEET OF AREA TO BE |
| | DRAINED, PLUS 1 CUBIC FOOT FOR EACH ADDITIONAL 100 |
| | SQUARE FEET OF AREA TO BE DRAINED INTO THE SEPARATOR- |
| | SEC. 1003.4.2- 1003.4.2.2 FBC P. |
| | |
| | A) SUBMIT SPECS FOR THE UNIT AND THE TRAFFIC LIDS- SEC. |
| | 1003.4.2. |
| | |
| | B) SHOW VENTING FOR THE UNIT- SEC. 1003.9. |
| | |
| | 11) A105 & P203: PROVIDE ROOF DRAINAGE CALCULATIONS FOR |
| | THE SERVICE DRIVE SECTION OF THE BUILDING AND SCUPPER |
| | AND OVERFLOW SIZES AND INSTALLATION DETAILS- SEC. |
| | 1106.1 FBC P. |
| | |
| | 12) A106 & P401: PROVIDE ROOF DRAINAGE CALCULATIONS FOR |
| | THE CAR WASH BUILDING AND GUTTER AND DOWNSPOUT SIZES- |
| | SECS, 1106.1, 1106.3 & 1106.6 FBC P. |
| | |
| | 13) P401 CAR WASH: PLEASE PROVIDE A SCHEDULE THAT |
| | CORRELATES WITH THE CIRCLED NUMBERS SHOWN ON THE PLAN- |
| | SEC. 107.2.1 WPB. |
| | |
| | 14) P401: PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS |
| | FOR THE HOLDING TANKS, AND ACCESS LIDS- SECS. 1301.9.2, |
| | 1301.9.6 FBC P. PLEASE NOTE THE ACCESS LIDS SHALL |
| | APPROVED LOCKING DEVICES OR OTHER APPROVED METHOD OF |
| | SECURING ACCESS. A) REFER TO SEC. 1301.9.9 AND PROVIDE |
| | MARKING AND SIGNAGE DETAILS FOR THE TANKS. |
| | |
| | 15) P401: PROVIDE PIPING SPECIFICATIONS FOR THE |
| | RECLAIM/REUSE SYSTEM- SEC. 1301.6 FBC P. |
| | |
| | 16) P401: TO HELP EXPEDITE THE REVIEW PLEASE PROVIDE AN |
| | ISOMETRIC DRAWING OR PIPING SCHEMATIC FOR THE WATER |
| | RECLAIM/REUSE SYSTEM- SEC. 1301.4 FBC P. |
| | |
| | 17) P401: PROVIDE TANK VENTING DETAILS- SEC. 1301.9.7 |
| | FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |