| Plan Review Notes For Permit 23040294 |
| Permit Number |
23040294 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2023-07-06 10:03:47 | PLAN DENIED | | | 1) PROVIDE A COMPLETE ENERGY CALCULATION FOR THE | | | PROJECT. | | | ONLY SHEETS 1 AND 2 OF 14 WERE SIBMITTED FEC 2020 | | | C403.2.1 | | | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATION | | | FOR THIS PROJECT FEC 2020 C 403.2.1 | | | 3) PLEASE SHOW ON THE PLAN THE LOCATION OF THE | | | CARBON MONOXIDE AND NITROGEN DIOXIDE DETECTORS. | | | SECTION 107 FBC. | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|