| 2023-04-28 08:51:25 | 1ST REVIEW FMC |
| | PERMIT: 23040294 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE THE COMPLETE ENERGY CALCULATIONS FOR THIS |
| | PROJECT. ONLY SHEETS 1 AND 2 OF 14 WERE SUBMITTED FEC |
| | C403.2.1 |
| | |
| | 2) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| | FOR THIS PROJECT. FEC C403.2.1 |
| | |
| | 3) SHEET M201 B: PROVIDE THE SEPARATE DESIGN AND SIZE |
| | OF THE SOURCE CAPTURE SYSTEM FOR THE USE IN THIS |
| | BUILDING. THERE APPEARS TO BE 44 LIFTS IN THIS SPACE |
| | BUT ONLY 12 HOSE REELS FOR THE SOURCE CAPTURE SYSTEM. |
| | FMC 502.14 |
| | |
| | 4) SHEET M202: PROVIDE GUARDS FOR ALL EQUIPMENT ON THE |
| | ROOF WITHIN 10 OF THE ROOFS EDGE. FMC 304.11 |
| | |
| | 5) SHEET M202: PROVIDE VEHICULAR PROTECTION FOR THE |
| | MECHANICAL SYSTEMS INSTALLED ON THE TOP FLOOR OF THE |
| | PARKING GARAGE. FMC 303.4 |
| | |
| | 6) SHEET M201 B: REMOVE ADD ALTERNATE NOTE FROM |
| | DRAWING. PROVIDE THE DESIGN WITHOUT ALTERNATES. FBC |
| | 107.3.5 |
| | |
| | 7) PROVIDE THE VENTILATION CALCULATIONS FOR THIS ENTIRE |
| | BUILDING. FMC 403.3.1.1 |
| | |
| | 8) SHOW HOW THE MECHANICAL EXHAUST DESIGN FOR THIS |
| | REPAIR GARAGE MEETS THE REQUIREMENTS OF TABLE |
| | 403.3.1.1. THE VENTILATION SYSTEM SHALL BE DESIGNED TO |
| | SUPPLY THE REQUIRED RATE OF VENTILATION AIR |
| | CONTINUOUSLY DURING THE PERIOD THE BUILDING IS |
| | OCCUPIED, EXCEPT AS OTHERWISE STATED IN OTHER |
| | PROVISIONS OF THE CODE. FMC 403.3.1.1 |
| | |
| | 9) SHEET M201 B: PROVIDE THE EXHAUST DUCT DETAILS FOR |
| | THE DRYER IN THE COMP/OIL ROOM. FMC 504 |
| | |
| | 10) SHEET M601 INDICATES THAT EF-3 HAS A TOTAL EXHAUST |
| | OF 1300 CFMS FOR THE BATHROOMS. SHEET M201 A SHOWS A |
| | TOTAL CFMS OF ONLY 700. THERE IS A DIFFERENCE OF 600 |
| | CFMS. PLEASE SHOW HOW THIS DESIGN MEETS THE PRESSURE |
| | EQUALIZATION REQUIREMENT OF FMC 501.4 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |