| 2023-04-27 11:08:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A102- THERE IS AN INDICATION OF A FIRE RATED |
| | WALL ALONG THE SERVICE SHOP WALL THAT SEPARATES THE |
| | PARTS AREA; HOWEVER, THERE IS NO FIRE RATED WALL ALONG |
| | THE SERVICE WALL BY THE LOCKER ROOMS & TECH BREAKROOMS. |
| | |
| | THERE IS ALSO AN UNPROTECTED 4'8" OPENING ALONG THAT |
| | WALL. |
| | |
| | PER NFPA 101 CH 6, THERE IS REQUIRED SEPARATION OF |
| | OCCUPANCY AND SEPARATION OF HAZARD. |
| | |
| | ONE MAY ATTEMPT TO CALL THAT AREA ACCESSORY TO THE |
| | SERVICE SHOP BUT THE SERVICE SHOP IS OF HIGHER HAZARD |
| | AND RATED SEPARATION IS REQUIRED AS INDICATED FROM THE |
| | PARTS SECTION. |
| | |
| | THAT OPENING IS REQUIRED TO BE PROTECTED ACCORDING TO |
| | THE RATING. |
| | |
| | PER NFPA 101, CH 6: |
| | |
| | 6.2 HAZARD OF CONTENTS |
| | 6.2.1 GENERAL. |
| | 6.2.1.1 FOR THE PURPOSE OF THIS CODE, THE HAZARD OF |
| | CONTENTS SHALL BE |
| | THE RELATIVE DANGER OF THE START AND SPREAD OF FIRE, |
| | THE DANGER OF SMOKE |
| | OR GASES GENERATED, AND THE DANGER OF EXPLOSION OR |
| | OTHER OCCURRENCE |
| | POTENTIALLY ENDANGERING THE LIVES AND SAFETY OF THE |
| | OCCUPANTS OF THE |
| | BUILDING OR STRUCTURE. |
| | |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF HAZARD |
| | OF CONTENTS EXIST IN DIFFERENT PARTS OF A BUILDING OR |
| | STRUCTURE, THE MOST |
| | HAZARDOUS SHALL GOVERN THE CLASSIFICATION, UNLESS |
| | HAZARDOUS AREAS ARE |
| | SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND |
| | THE APPLICABLE |
| | SECTIONS OF CHAPTERS 11 THROUGH 43. |
| | |
| | 6.2.2 CLASSIFICATION OF HAZARD OF CONTENTS. |
| | 6.2.2.1* GENERAL. THE HAZARD OF CONTENTS OF ANY |
| | BUILDING OR STRUCTURE |
| | SHALL BE CLASSIFIED AS LOW, ORDINARY, OR HIGH IN |
| | ACCORDANCE WITH 6.2.2.2, |
| | 6.2.2.3, AND 6.2.2.4 |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND CODE |
| | REFERENCES OF PROVIDE THE REQUIRED FIRE RATING ALONG |
| | THE REMAINDER OF THE WALL. |
| | |
| | |
| | |
| | 2) SHEET E201 - THERE IS AN INDICATION OF AN EXIT SIGN |
| | WITHIN THE CORRIDOR OVER DOOR # 107 LEADING INTO THE |
| | SERVICE ADVISORS AREA. |
| | |
| | THAT DOOR SWINGS AGAINST THE PATH OF TRAVEL. |
| | |
| | ALL OTHER EXIT DOORS SWING IN THE PATH OF TRAVEL. |
| | |
| | PER NFPA 101, CH 77.2.1.4.2* DOOR LEAF SWING DIRECTION. |
| | DOOR LEAVES REQUIRED TO BE OF |
| | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN |
| | THE DIRECTION |
| | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR MORE, |
| | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY |
| | 7.2.4.3.8.1 |
| | OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO SWING |
| | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH |
| | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS THE |
| | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS DIRECTLY |
| | INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS AND CODE |
| | REFERENCES OR CORRECT THE SWING DIRECTION. |
| | |
| | |
| | 3) SHEET FS201 - THERE APPEARS TO BE AB INDICATION OF A |
| | SINGLE CLASS 1 2 1/2' HOSE CONNECTION IN THE CENTER OF |
| | THE PARKING GARAGE. |
| | |
| | PER NFPA 1 |
| | |
| | 13.2 STANDPIPE SYSTEMS. |
| | 13.2.1 GENERAL. THE DESIGN AND INSTALLATION OF |
| | STANDPIPE SYS TEMS SHALL BE IN ACCORDANCE WITH SECTION |
| | 13.2 AND NFPA 14, |
| | STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE |
| | SYSTEMS. |
| | 13.2.2 WHERE REQUIRED. |
| | 13.2.2.1 WHERE REQUIRED BY THIS CODE OR THE REFERENCED |
| | CODES |
| | AND STANDARDS LISTED IN CHAPTER 2, STANDPIPE SYSTEMS |
| | SHALL BE |
| | INSTALLED IN ACCORDANCE WITH 13.2.1. |
| | 13.2.2.2 NEW BUILDINGS SHALL BE EQUIPPED WITH A CLASS I |
| | STAND PIPE SYSTEM INSTALLED IN ACCORDANCE WITH THE |
| | PROVISIONS OF SEC TION 13.2 WHERE ANY OF THE FOLLOWING |
| | CONDITIONS EXIST: |
| | (1) MORE THAN THREE STORIES ABOVE GRADE WHERE THE |
| | BUILDING IS |
| | PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | (2) MORE THAN TWO STORIES ABOVE GRADE WHERE THE |
| | BUILDING IS |
| | NOT PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM |
| | (3) MORE THAN 50 FT (15 M) ABOVE GRADE AND CONTAINING |
| | INTER MEDIATE STORIES OR BALCONIES |
| | (4) MORE THAN ONE STORY BELOW GRADE |
| | (5) MORE THAN 20 FT (6.1 M) BELOW GRADE |
| | |
| | PER NFPA 14 |
| | |
| | 7.3 LOCATIONS OF HOSE CONNECTIONS. |
| | 7.3.1* GENERAL. |
| | 7.3.1.1 HOSE CONNECTIONS AND HOSE STATIONS SHALL BE |
| | UNOB STRUCTED AND SHALL BE LOCATED NOT LESS THAN 3 FT |
| | (0.9 M) OR MORE |
| | THAN 5 FT (1.5 M) ABOVE THE FLOOR. |
| | 7.3.1.1.1 THIS DIMENSION SHALL BE MEASURED FROM THE |
| | FLOOR TO |
| | THE CENTER OF THE HOSE VALVE. |
| | |
| | 7.3.2* CLASS I SYSTEMS. CLASS I SYSTEMS SHALL BE |
| | PROVIDED WITH |
| | 21???2 IN. (65 MM) HOSE CONNECTIONS IN THE FOLLOWING |
| | LOCATIONS: |
| | (1) AT THE MAIN FLOOR LANDING IN EXIT STAIRWAYS |
| | (2) ON EACH SIDE OF THE WALL ADJACENT TO THE EXIT |
| | OPENINGS OF |
| | HORIZONTAL EXITS |
| | (3) IN OTHER THAN COVERED MALL BUILDINGS, IN EACH EXIT |
| | PAS SAGEWAY AT THE ENTRANCE FROM THE BUILDING AREAS |
| | INTO THE |
| | PASSAGEWAY |
| | (4) IN COVERED MALL BUILDINGS, AT THE ENTRANCE TO EACH |
| | EXIT |
| | PASSAGEWAY OR EXIT CORRIDOR, AND AT THE INTERIOR SIDE |
| | OF |
| | PUBLIC ENTRANCES FROM THE EXTERIOR TO THE MALL |
| | (5)*AT THE HIGHEST LANDING OF STAIRWAYS WITH STAIRWAY |
| | ACCESS TO A |
| | ROOF, OR ON ROOFS WITH A SLOPE OF LESS THAN 4 IN 12 |
| | WHERE |
| | STAIRWAYS DO NOT ACCESS THE ROOF |
| | |
| | 7.3.2.3* HOSE CONNECTIONS ON ONE SIDE OF A HORIZONTAL |
| | EXIT |
| | SHALL NOT BE REQUIRED WHERE ANOTHER OUTLET ON THAT SIDE |
| | OF THE |
| | HORIZONTAL EXIT CAN REACH THE PORTIONS OF THE BUILDING |
| | ON THE |
| | OTHER SIDE OF THE HORIZONTAL EXIT WITHIN THE DISTANCES |
| | REQUIRED |
| | BY 7.3.2.3.1 THAT WOULD HAVE BEEN PROTECTED BY THE |
| | OUTLET THAT |
| | WAS OMITTED. |
| | 7.3.2.3.1 THIS TRAVEL DISTANCE SHALL BE 200 FT (61 M) |
| | FOR |
| | SPRINKLERED BUILDINGS AND 130 FT (39.7 M) FOR NONSPRIN |
| | KLERED BUILDINGS |
| | |
| | PLEASE REVIEW AND PROVIDE HOSE CONNECTION WITHIN THE |
| | STAIRWELLS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |