| 2023-05-01 14:29:53 | ELECTRIC REVIEW FAILED |
| | |
| | 1) ONE LINE DIAGRAM ON SHEET E501 DETAILS A PORTABLE |
| | GENERATOR SERVICE ENTRANCE RATED DOCKING TRANSFER |
| | SWITCH. THIS APPEARS TO BE THE SERVICE EQUIPMENT |
| | DISCONNECTING MEANS AS DEFINED IN ACCORDANCE WITH NEC |
| | 100 DEFINITIONS, SERVICE EQUIPMENT IS DEFINED AS, THE |
| | NECESSARY EQUIPMENT, USUALLY CONSISTING OF A CIRCUIT |
| | BREAKER(S) OR SWITCH(ES) AND FUSE(S) AND THEIR |
| | ACCESSORIES, CONNECTED TO THE LOAD END OF SERVICE |
| | CONDUCTORS TO A BUILDING OR OTHER STRUCTURE, OR AN |
| | OTHERWISE DESIGNATED AREA, AND INTENDED TO CONSTITUTE |
| | THE MAIN CONTROL AND CUTOFF OF THE SUPPLY. |
| | THIS TRANSFER SWITCH IS DETAILED AS BEING RATED AT |
| | 1200 AMPS AND 480 VOLTS, HOWEVER NOT DETAILED AS HAVING |
| | GROUND FAULT PROTECTION IN ACCORDANCE WITH NEC 215.10 |
| | AND NEC 230.95 |
| | ONE LINE DIAGRAM ON SHEET E501 DETAILS TWO SERVICES TO |
| | BUILDING, ONE SERVICE IS DETAILED AS HEVA, THE OTHER |
| | SERVICE IS THE TRANSFER SWITCH FEEDING MAIN |
| | DISTRIBUTION PANEL HDPA. THE TRANSFER SWITCH IS |
| | DETAILED AS BEING OUTSIDE AND SERVICE HEVA IS ON THE |
| | INSIDE OF THE BUILDING. THIS DOES NOT COMPLY WITH NEC |
| | 230.72 FOR GROUPING OF SERVICES. |
| | ONE LINE DIAGRAM DETAILS SYSTEM BONDING JUMPER FROM |
| | GROUNDED CONDUCTOR IN MAIN DISTRIBUTION PANEL HDPA, |
| | HOWEVER, THE BONDING OF THE GROUNDING CONDUCTOR SHOULD |
| | BE DETAILED AT THE TRANSFER SERVICE DISCONNECTING |
| | SWITCH IN ACCORDANCE WITH NEC 250.30 (A)(1) |
| | IT APPEARS THIS ELECTRICAL SERVICE SYSTEM WILL NEED TO |
| | RECONFIGURE TO COMPLY WITH THE NEC REQUIREMENTS |
| | OUTLINED ABOVE. |
| | |
| | 2) PLEASE PROVIDE AN AVAILABLE FAULT CURRENT |
| | CALCULATION IS REQUIRED IN ACCORDANCE WITH NEC 110.10. |
| | IN ADDITION, PLEASE PROVIDE A NOTE STATING COMPLIANCE |
| | WITH FIELD MARKING AS REQUIRED IN ACCORDANCE WITH NEC |
| | 110.16(B) |
| | |
| | 3) PLEASE PROVIDE A NOTE STATING COMPLIANCE WITH |
| | UNDERGROUND WIRING LOCATED IN CLASS 1 HAZARDOUS |
| | LOCATION AREAS, IN ACCORDANCE WITH NEC 511.8 EXCEPTION |
| | FOR CONDUIT TYPES AND COVERAGE REQUIREMENTS OF 2 FEET |
| | |
| | 4) PLEASE PROVIDE A NOTE STATING, GENERATORS, SITE |
| | LIGHTING, FIRE ALARM, DATA, VOICE AND ALL OTHER TYPES |
| | OF LOW VOLTAGE WIRING REQUIRE SEPARATE PERMITS. |
| | |
| | 5) PLEASE DETAIL CAR CHARGING STATIONS AND PARKING |
| | COMPLY WITH FBC ACCESSIBILITY. NOTE: THE BUILDING |
| | OFFICIAL HAS DETERMINED THAT ACCESSIBLE CHARGING |
| | STATIONS ARE TO BE PROVIDED BASED ON THE NUMBER OF |
| | CHARGING STATIONS PROVIDED AT EACH LOCATION USING FBC |
| | ACCESSIBILITY TABLE 208.2. IF THERE ARE BETWEEN 1 - 25 |
| | PARKING SPACES PROVIDED WITH CHARGING STATIONS, THEN 1 |
| | SUCH SPACE MUST BE ACCESSIBLE. ADVISORY 208.2 MINIMUM |
| | NUMBER. THE TERM "PARKING FACILITY" IS USED IN SECTION |
| | 208.2 INSTEAD OF THE TERM "PARKING LOT" SO THAT IT IS |
| | CLEAR THAT BOTH PARKING LOTS AND PARKING STRUCTURES ARE |
| | REQUIRED TO COMPLY WITH THIS SECTION. THE NUMBER OF |
| | PARKING SPACES REQUIRED TO BE ACCESSIBLE IS TO BE |
| | CALCULATED SEPARATELY FOR EACH PARKING FACILITY; THE |
| | REQUIRED NUMBER IS NOT TO BE BASED ON THE TOTAL NUMBER |
| | OF PARKING SPACES PROVIDED IN ALL OF THE PARKING |
| | FACILITIES PROVIDED ON THE SITE. |
| | |
| | 6) PLEASE DETAIL COMPLIANCE WITH NEC 625.43, ELECTRIC |
| | VEHICLE CHARGING SYSTEM DISCONNECTING MEANS IS READILY |
| | ACCESSIBLE AND LOCKABLE IN ACCORDANCE WITH NEC 110.25 |
| | |
| | 7) PLEASE DETAIL BY NOTE, COMPLIANCE WITH NEC 702.7(C) |
| | FOR WARNING SIGN PLACEMENT, FOR PORTABLE GENERATOR |
| | POWER INLET, DETAILING TYPE OF DERIVED SYSTEM THE |
| | SYSTEM IS CAPABLE OF BASED ON THE WIRING OF THE |
| | TRANSFER EQUIPMENT. |
| | |
| | 8) PLEASE INDICATE WHO WILL BE INSTALLING VEHICLE |
| | CHARGERS, I.E., WILL IT BE A DIFFERENT ELECTRICAL |
| | CONTRACTOR. THIS INFORMATION IS REQUIRED TO DETERMINE |
| | WHETHER A SEPARATE PERMIT WILL BE REQUIRED FOR THERE |
| | INSTALLATION. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |
| | |