| Notes |
| Date |
Text |
| 2023-06-15 09:45:39 | ROOF OVER | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE DRAWINGS SHOW A WIND PRESSURE FOR WIND ZONE 3' | | | AS (-152) - THE ROOF PANEL PRODUCT APPROVAL SHOWS A | | | MAXIMUM WIND DESIGN PRESSURE OF (-142) WHICH IS LOWER | | | THAN THE PRESSURE ON THE DRAWING - PLEASE CLARIFY HOW | | | THIS MEETS REQUIREMENTS PER FBC 1609 |
|